3.3.6 Alarm handling

Max. three alarms can be configured and assigned to the individual outputs. Ge-
nerally, outputs

OuT.1... OuT.3 can be used each for alarm signalling. If more

than one signal is linked to one output the signals are OR linked. Each of the 3 li-
mit values

Lim.1 … Lim.3 has 2 trigger points H.x (Max) and L.x (Min), which

can be switched off individually (parameter = “

OFF”). Switching difference

HYS.x of each limit value is adjustable.

normally closed (

ConF / Out.x / O.Act = 0 )

normally open

(

ConF / Out.x / O.Act = 1 )

Operation

Digital 280-1

Operating level

15

H.1

LED

HYS.1

InL.1

InH.1

Operaing principle absolut alarm

L.1 = OFF

LED

HYS.1

H.1

InL.1

InH.1

SP

Operating principle relative alarm

L.1 = OFFF

L.1

LED

HYS.1

InL.1

InH.1

H.1 = OFF

L.1

LED

HYS.1

InL.1

InH.1

SP

H.1 = OFF

L.1

LED

LED

HYS.1

HYS.1

H.1

InL.1

InH.1

L.1

LED

LED

HYS.1

HYS.1

H.1

InL.1

InH.1

SP