Page 21

The control parameters can be determined from the values calculated for delay
time T
u
, maximum rate of increase v
max
, control range X
h
and characteristic K ac-
cording to the formulas given below. Increase Xp, if line-out to the set-point os-
cillates.
Controller
Digital 280-1
Manual tuning
21
Formulas
K = Vmax * Tu
controller behavior Pb1 [phy. units]
td1 [s]
ti1 [s]
With 2-point and
3-point controllers,
the cycle time must
be adjusted to
t1 / t2 £ 0,25 * Tu
PID
1,7 * K
2 * Tu
2 * Tu
PD
0,5 * K
Tu
OFF
PI
2,6 * K
OFF
6 * Tu
P
K
OFF
OFF
3-point-stepping
1,7 * K
Tu
2 * Tu
Parameter adjustment effects
Parameter
Control
Line-out of disturbances
Start-up behaviour
Pb1 higher increased damping
slower line-out
slower reduction of duty cycle
lower
reduced damping
faster line-out
faster reduction of duty cycle
td1 higher reduced damping
faster response to disturbances faster reduction of duty cycle
lower
increased damping
slower response to disturbances slower reduction of duty cycle
ti1 higher increased damping
slower line-out
slower reduction of duty cycle
lower
reduced damping
faster line-out
faster reduction of duty cycle