5
PROFIBUS SETTINGS
48
UFC 400
www.krohne.com
05/2014 - 4003118502 - AD UFC 400 PROFIBUS R02 en
C4 I/O PROFIBUS
C4
I/O PROFIBUS
Using the menu functions mentioned below you will be able to control
basically the five analog input blocks of this PROFIBUS device. These eights
menus are identical so they are grouped together and their functions are
described in one go.
C4.1
FB1 Analog Inp.
There are 6 analog input blocks.
_ stands for the 6 analog input blocks: FB1 (_ = 1), FB2 (_ = 2), FB6 (_ = 3),
FB7 (_ = 4), FB8 (_ = 5), FB9 (_ = 6)
C4.2
FB2 Analog Inp.
C4.3
FB6 Analog Inp.
C4.4
FB7 Analog Inp.
C4.5
FB8 Analog Inp.
C4.6
FB9 Analog Inp.
C4._.1
Measurement
Select measurement value for the analog input blocks:
Volume Flow / Mass Flow / Velocity of Sound / Flow Speed / Gain /
SNR / Electr. Temperature / Supply
C4._.2
Time Constant
Set time constant for this function block (_).
C4._.3
Error Behaviour
Defines the behaviour of this function block in case of errors.
Select: hold value / ignore error / replace value
hold value:
hold value:
hold value:
hold value: Last valid OUT value stored will be used as OUT value.
ignore error:
ignore error:
ignore error:
ignore error: OUT has the wrong calculated value and status "Bad" as
calculated.
replace value:
replace value:
replace value:
replace value: The "replacement value" will be used as OUT value.
C4._.4
Replacement Value
Available, if the error behaviour "Replace Value" is selected. Defines the
value that replaces the measured value at this function block in case of an
error.