PROFIBUS PA

22

UFC 400

www.krohne.com

05/2014 - 4003118502 - AD UFC 400 PROFIBUS R02 en

Profile specific Ident. Number (9741 hex)

Functionality is reduced to the requirements which are mandatory in the PA Profile; e.g. 2 x AI-
FB and 1 x TOT-FB are available for cyclic data transfer only. Device specific diagnosis
information is not available via cyclic PROFIBUS services. Nevertheless this behaviour will
improve interchangeability between devices of different vendors because only functions are
available which are provided by all PROFIBUS PA ultrasonic flowmeters. Exchange is possible
without modifying the configuration of the control system.

Cyclic layout:

Valid GSD Modules:

GSD File required:

GSD file PA139741.GSD

PA139741.GSD

PA139741.GSD

PA139741.GSD is required in this mode. This file is provided by PROFIBUS International.

Take care that "Condensed Status and Diagnosis" is not supported by this file.

INFORMATION!
During network configuration the user has to define which function block outputs of the signal
converter should be transferred cyclically to the master. This is performed by a bus
configuration tool (e.g. "HW- Config" for PC S7 from Siemens). This tool offers specific functions
as follows:
1. It is possible to configure an "Empty block" (the code of an "Empty" block is defined as 0x00) on

each block number. This implies: no data is transmitted in the cyclic data telegram for this
block.

2. There is NO "Totaliser (TOT)" function block allowed on block position 1, 2, 6, 7, 8, 9! On these

positions, only an "Analog Input (AI)" function block or an "Empty" block is allowed!
(Note: All codes supported by "Analog Input (AI)"

and "Totaliser (TOT)"

function blocks will

be found in the corresponding GSD files.)

3. There is NO "Analog Input (AI)" function block allowed on block position 3, 4 and 5! On these

positions, only a "Totaliser (TOT)" function block or an "Empty" block is allowed!

4. There is a choice of 7 different totaliser functions, which can be allocated to the blocks 3, 4

and/or 5.

Slot

Description

Function Block type

Default unit

1

Volume Flow

AI-FB

m

3

/h

2

Velocity of sound

AI-FB

m/s

3

Totaliser

Totaliser-FB

m

3

AI-FB

EMPTY_MODULE
AI

Totaliser-FB

EMPTY_MODULE
TOTAL
SETTOT_TOTAL
SETTOT_MODETOT_TOTAL

INFORMATION!
If another GSD file is used in the PROFIBUS master system the cyclic data transfer cannot be
established in this setting.