COMMISSIONING / OPERATION

32

UFC 400

www.krohne.com

05/2014 - 4003118502 - AD UFC 400 PROFIBUS R02 en

40

2

Maintenance alarm

The device or measurement is defective and cannot measure.

Related output values are invalid. Typically a repair or

replacement of the device is required.

Check detailed diagnosis. Restart the device. If the error occurs

again: send the device back to the manufacturer with an

indication of the error.

41

2

Maintenance demanded

The device or application condition is in a way that the

measurement accuracy may be reduced. But still the

measurement value follows the source. E.g. the device may be

operated outside its specified operating range.

Check detailed diagnosis. Restart the device. If the error occurs

again: send the device back to the manufacturer with an

indication of the error.

42

2

Function check

Simulation is active. Disable simulation to clear this message.

55

yes

Extension available

Refer to detailed diagnosis in bits 56 to 103.

56

3

C – Process

(classification fixed - not changeable)

Process related "Function check" running. E.g. the measurement

values may be simulated values for a currently performed check.

The related output values are temporarily invalid. Turn off

"Function check" to change back into measurement mode / 6.

57

3

C – Configuration

(classification fixed - not changeable)

Configuration related "Function check" running. E.g. the

measurement values may be simulated values for a currently

performed check. The related output values are temporarily

invalid. Turn off "Function check" to change back into

measurement mode / 6.

58

3

C – Electronics

(classification fixed - not changeable)

Converter Electronics related "Function check" running. E.g. the

measurement values may be simulated values for a currently

performed check. The related output values are temporarily

invalid. Turn off "Function check" to change back into

measurement mode / 6.

59

3

C – Sensor

(classification fixed - not changeable)

Sensor related "Function check" running. E.g. the measurement

values may be simulated values for a currently performed check.

The related output values are temporarily invalid. Turn off

"Function check" to change back into measurement mode / 6.

60

3

F – Process

(classification fixed - not changeable)

Process related settings are defective. Related output values are

invalid. A repair or replacement of the device can be necessary.

Check process parameters / 4 - restart the device – if the error

still occur contact the service department of the manufacturer.

61

3

F – Configuration

(classification fixed - not changeable)

Configuration is defective. Related output values are invalid. A

repair or replacement of the device can be necessary. Check

configuration / 4 - restart the device – if the error still occur

contact the service department of the manufacturer.

62

3

F – Electronics

(classification fixed - not changeable)

Converter Electronic is defective and not able to measure.

Related output values are invalid. Typically a repair or

replacement of the device is required. Check converter / 4 -

restart the device – if the error still occur send back the device to

the manufacturer with an indication of the error.

63

3

F – Sensor

(classification fixed - not changeable)

Sensor is defective and not able to measure. Related output

values are invalid. Typically a repair or replacement of the device

is required. Check sensor / cabling / 4 - restart the device – if the

error still occur send back the device to the manufacturer with an

indication of the error.

64

3

M – Process

(classification fixed - not changeable)

Process related problem(s) detected. But still the measurement

values are accurate. The output values are still valid, but this may

change in the near future. Check problem(s) / 5 - if the

problem(s) cannot be fixed contact the service department of the

manufacturer with an indication of the problem(s).

Bit Number

sup

p

orted

De

sc

ription

Remedy