4.3 Diagnosis

The PROFIBUS device performs internal self-tests. The results are provided as detailed
diagnosis information according to PA Profile 3.02. This diagnosis information is available via
several parameters and can be read by an engineering tool (e.g. DD/DTM). In addition the
diagnosis information is transferred via cyclic services towards the control system (e.g. PLC).

Diagnosis is bitwise coded. Therefore it is possible to report more than one indication
simultaneously. The GSD file contains a text for each diagnosis bit in order to provide a text
message in the control system. The references are defined by the UNIT_DIAG_BIT(i) entries.
They show which bit is set to indicate a special diagnosis event.

The amount and content of the diagnosis information depends on the device configuration. The
active Ident. Number and the selected status and diagnosis mode will influence diagnosis
propagation. The following tables show the diagnosis events which are reported for different
settings. The bit number is equal to the counting within the GSD file. It represents the position in
the device-related diagnostic field of the Slave_Diag service.

Bit Number

sup

p

orted

De

sc

ription

Remed

y

16

yes

Error appears

-

17

yes

Error disappears

-

24

1

Hardware failure electronics

The device or measurement is defective and cannot measure.

Related output values are invalid. Typically a repair or

replacement of the device is required.

Check detailed diagnosis. Restart the device. If the error occurs

again: send the device back to the manufacturer with an

indication of the error.

29

1

Measurement failure

The device or application condition is in a way that the

measurement accuracy may be reduced. But still the

measurement value follows the source. E.g. the device may be

operated outside its specified operating range.

Check detailed diagnosis. Restart the device. If the error occurs

again: send the device back to the manufacturer with an

indication of the error.

35

yes

Restart

Device is restarted because of power-up or warmstart request. In

case of unexpected restart: send the device back to the

manufacturer with an indication of the error.

36

yes

Coldstart

Device is reset to its Factory/Default settings because of a user

request. Recover user specific parameter settings.

37

yes

Maintenance required

The device detects problem(s), which are less severe compared to

the diagnosis "Measurement failure". But still the measurement

values are accurate. The output values are still valid, but this may

change in the near future. Check detailed diagnosis to solve the

problem.

39

yes

Ident_Number violation

Ident. Number Selector was modified while cyclic data transfer

was active. To clear this message perform one of the following

actions:

Reset Ident. Number Selector to its former setting

Stop cyclic data transfer

Restart the device