The C95 CI is a totalling digital panel meter. The totalling function allows
converting any instant value, after integration, into a cumulated magnitu-
de.
It can be connected to a flowmeter to display the instant flow and the
cumulated volume or weight, and also to a converter, for instance a
power converter to display the instant power and the energy consump-
tion of an installation.
General features
- Instant value display on 5 digits (14mm) with scale factor adjusting
from -99 999 to 99 999
- Cumulated value display on a 6 digit counter (14mm) associated with
a second overstepping counter, allows totalling from -99 999 999 to
+999 999 999
- Totalizer memory saved in case of power supply cut
- Programming of the integration time (sec, min, hours) and of
a convertion coefficient (from 0,0001 to 999999)
- A bargraph allows a quick evaluation either of the instant value or
the cumulated value, and can also be used as indicator for various
functions (overstepping, LOGIC input, RS, etc...)
• Input :
- Direct current or voltage, bidirectionnal
±100mV, ±1V, ±10V, ±300V, ±20mA
- Measurable scale overstepping from -5% to +5%
- Input impedance
≥1MΩ for voltage inputs
drop 0.9V max for the current input
- Enlarging effect possible
- Linear input with or without square root extraction and special curve
on 20 pt (programmable in X and in Y).
- Supply for 2 or 3 wire sensor for the current input : 26 VDC (±15%)
100mA protected from short-circuits.
11.. IIN
NT
TR
RO
OD
DU
UC
CT
TIIO
ON
N
• Transfer :
- Accuracy 0.05% of full scale at 25°C
- Thermic drift <150 ppm / °C
- Sampling time : 100ms
- Filtering : Programmable integration time (10 coefficients)
- Common mode rejection rate : 130 dB
- Serial mode rejection rate : 70 dB 50/60 Hz
- Insulation : Input / Power supply : 2.5kV 50 Hz 1 min
Input / Output : 2.5kV eff. 50 Hz 1 min
A
AV
VA
AIILLA
AB
BLLE
E O
OP
PT
TIIO
ON
NS
S
:
(specify on order)
Insualted analog output : A
Programmable on the instant or cumulated value
Active current output
Programmable scale ratio with enlarging effect.
Relay output 2 relays (R)
Programmable :
- As Pulse output with adjusting of the pulse weight
(-10 000 to +10 000) and of its duration
(100, 200 or 400 ms)
- In mode alarm on the instant or cumulated value
Mode setpoint or window.
Recording of alarms.
Time delay and hysteresis adjustable on each setpoint.
Alarm messages
Insulated digital output : N
RS 485 2 wire, protocole MODBUS-JBUS.
LOGIC input 2 insulated LOGIC inputs with programmable functions
Several types of totalizer zero reset
Integration stop and start
Display blocking
Display switching (instant value / totalizer)
Function tare,
min. and max. zero reset