S

The C95 CI is a totalling digital panel meter. The totalling function allows

converting any instant value, after integration, into a cumulated magnitu-

de.

It can be connected to a flowmeter to display the instant flow and the

cumulated volume or weight, and also to a converter, for instance a

power converter to display the instant power and the energy consump-

tion of an installation.

General features

- Instant value display on 5 digits (14mm) with scale factor adjusting

from -99 999 to 99 999
- Cumulated value display on a 6 digit counter (14mm) associated with

a second overstepping counter, allows totalling from -99 999 999 to

+999 999 999
- Totalizer memory saved in case of power supply cut

- Programming of the integration time (sec, min, hours) and of

a convertion coefficient (from 0,0001 to 999999)

- A bargraph allows a quick evaluation either of the instant value or

the cumulated value, and can also be used as indicator for various

functions (overstepping, LOGIC input, RS, etc...)

• Input :
- Direct current or voltage, bidirectionnal

±100mV, ±1V, ±10V, ±300V, ±20mA

- Measurable scale overstepping from -5% to +5%

- Input impedance

≥1MΩ for voltage inputs

drop 0.9V max for the current input

- Enlarging effect possible
- Linear input with or without square root extraction and special curve

on 20 pt (programmable in X and in Y).
- Supply for 2 or 3 wire sensor for the current input : 26 VDC (±15%)

100mA protected from short-circuits.

11.. IIN

NT

TR

RO

OD

DU

UC

CT

TIIO

ON

N

• Transfer :
- Accuracy 0.05% of full scale at 25°C

- Thermic drift <150 ppm / °C

- Sampling time : 100ms

- Filtering : Programmable integration time (10 coefficients)

- Common mode rejection rate : 130 dB

- Serial mode rejection rate : 70 dB 50/60 Hz

- Insulation : Input / Power supply : 2.5kV 50 Hz 1 min

Input / Output : 2.5kV eff. 50 Hz 1 min

A

AV

VA

AIILLA

AB

BLLE

E O

OP

PT

TIIO

ON

NS

S

:

(specify on order)

Insualted analog output : A

Programmable on the instant or cumulated value

Active current output

Programmable scale ratio with enlarging effect.

Relay output 2 relays (R)

Programmable :

- As Pulse output with adjusting of the pulse weight

(-10 000 to +10 000) and of its duration

(100, 200 or 400 ms)
- In mode alarm on the instant or cumulated value

Mode setpoint or window.

Recording of alarms.

Time delay and hysteresis adjustable on each setpoint.

Alarm messages

Insulated digital output : N

RS 485 2 wire, protocole MODBUS-JBUS.

LOGIC input 2 insulated LOGIC inputs with programmable functions

Several types of totalizer zero reset

Integration stop and start

Display blocking

Display switching (instant value / totalizer)

Function tare,

min. and max. zero reset