beautypg.com

KROHNE C95 CI EN User Manual

Page 24

background image

S

5.2.2 Tare setting (only on instant value display)

Press and to enforce the signal present on the input as display
down scale

Note : The tare is not recorded in case of power supply cut.
To suppress the tare, go into menu in the main menu p6.
Exit from mode programming with configuration saving will automatically
reset the tare to zero.

(accessible according to programmed access code)

d.dISP

CLr.tA

5.2.4 Direct measure visualising

Press and to visualise the signal directly without any processing

: scale factor, square root, linearisation
− in mV, V or mA.

M

M

5.2.3 Changing of the displayed value

Press and to switch from the instant value to the totalizer, and

vice-versa.
Led marking A blinking : instant value.
Led marking H blinking : totalizer

5.2.5 Visualisation and setting of alarm setpoints

Setting of setpoints : There are 2 ways to adjust setpoints.
- either in mode programming entering the correct safety access code

- or by simultaneous pressing on and

M

M

M

M

Option 22 rrelays

M

M

M

M

The meter will then show the message SP.x or SPx.x alternating with

the value of the corresponding setpoint.
The various setpoint values can be accessed by or .
These setpoints can then be changed (according to the programmed

access code, see p20) pressing
Once the setpoint is adjusted, press to revert to the setpoints rea-

ding menu.
Once all setpoints are adjusted, just press and the meter will revert

to mode measure, taking the new values into account.

If no key is pressed during 60 s., the meter will revert to measure

display without taking the modifications of setpoint values into account.

66.. E

ER

RR

RO

OR

R oorr iinnddiiccaattiioonn M

ME

ES

SS

SA

AG

GE

ES

S

2000
OPEn

Err.1

Value in overstepping

Sensor rupture

«

01000

Counting overstepping

> 999 999 999

or < -99 999 999

«

----

O.L.

Er.xxx

Input upper or lower electrical

overstepping
Displayable value overstep-

ping.
Self-diagnosis error

Value set out of range

On instant value display

On totalizer display

totalizer

OPEN

-----

Electrical overstepping or

sensor rupture recorded.

or