State of the totalizer
Value of the oversteppings counter
Value of the totalizer
Value of the analog output
in µA
Minimum value of the displayed
value
Maximum value of the displayed
value
Instant measure displayed
Direct measure
State of relay 1
State of relay 2

Format

integer
integer

double integer
double integer

double integer

double integer

double integer
double integer

integer
integer

nb of words

1
1
2
2

2

2

2
2
1
1

99.. A

AN

NN

NE

EX

XE

E :: M

MO

OD

DB

BU

US

S

9.1 Table of modbus addresses

•• Direct measure :
Value without scale factor for inputs 100 mV, 1V, 10V, 300V, 20 mA :

- in mV for the 10V input

- in 10

th

of mV for the 1V input

- in µA for the mA input

- in 100

th

of mV for the mV input

- in 100

th

of V for the 300V input

•• State of the relays :

bit 15

bit 7 bit 6

bit 0

1 : Led lit
1 : Led blinking : mode

recording and measure

not in alarm area
1 : Relays ON
Alarm recorded

•• Instant measure :
The instant measure value is shown on the display without the decimal point.

To read the decimal point value, read the word at address 120.

bit 15

bit 2 bit 1 bit 0

*Decimal point location

1 : Display with 4 decimals

2 : Display with 3 decimals

3 : Display with 2 decimals

4 : Display with 1 decimal

5 : Display with 0 decimals

•• Value of the totalizer :
The totalizer value is :

if value negative :

value of the oversteppings counter x -100 000 + totalizer value

if value positive :

value of the oversteppings counter x 1 000 000 + totalizer value

To know the decimal point, read the word at address 138.

Address 138 :

bit 15

bit 2 bit 1 bit 0

Location of the totalizer decimal point

1 : Display with 4 decimals

2 : Display with 3 decimals

3 : Display with 2 decimals

4 : Display with 1 decimal

5 : Display with 0 decimals

bit 15

bit 2 bit 1 bit 0

1: sensor rupture error

recorded
1: electrical overstep-

ping error recorded
positive overstepping of

the oversteppings

counter Hi.tot > 1000
negative overstepping

of the oversteppings

counter Hi.tot < -1000

•• State of the totalizer :

bit 4

bit 5

bit 3

totalizer overstepping

(oversteppings counter

Hi.tot

≠ 0)

Address 120 :