beautypg.com

Operation – KROHNE IFC 300 Converter FOUNDATION FIELDBUS EN User Manual

Page 45

background image

OPERATION

4

45

IFC 300

www.krohne.com

02/2011 - 4001086501 - AD IFC 300 FF R02 en

BKCAL_HYS

BKCAL_HYS

BKCAL_HYS

BKCAL_HYS

Back Calculation

Back Calculation

Back Calculation

Back Calculation

Hysteresis

Hysteresis

Hysteresis

Hysteresis

R/W

Limits the minimum output value for modes other than

"Manual". The limit status is turned off, expressed as a

percent of the span of the output.

0.5

Setting:

0.0...50.0%

BKCAL_IN

BKCAL_IN

BKCAL_IN

BKCAL_IN

Back Calculation

Back Calculation

Back Calculation

Back Calculation

Input

Input

Input

Input

R/W

The value and status used for backwards tracking of the

output, provided by a link to the back calculation output

parameter of a downstream block.

-

Status

R/W

Status of BKCAL_IN

-

Value

R/W

Value of BKCAL_IN

-

BKCAL_IN

BKCAL_IN

BKCAL_IN

BKCAL_IN

Back Calculation

Back Calculation

Back Calculation

Back Calculation

Input

Input

Input

Input

R

The output value and status provided to an upstream block for

output tracking when the loop is broken or limited, as

determined by the status bits. This information is used to

provide bumpless transfer to closed loop control and to

prevent windup under limited conditions when that becomes

possible.

-

Status

R

Status of BKCAL_OUT

-

Value

R

Value of BKCAL_OUT

-

BLOCK_ALM

BLOCK_ALM

BLOCK_ALM

BLOCK_ALM

Block Alarm

Block Alarm

Block Alarm

Block Alarm

R/W

The block alarm is used for all configuration, hardware,

connection failure or system problems in the block. The cause

of the alert is entered in the subcode field. The first alert to

become active will set the "Active" status in the "Status"

attribute. As soon as the "Unreported" status is cleared by the

alert reporting task, another block alert may be reported

without clearing the "Active" status, if the subcode has

changed.

-

Unacknowledged

R/W

A discrete enumeration which is set to "Unacknowledged"

when an alarm occurs, and set to "Acknowledged" by a write

from a human interface device or other entity which can

acknowledge that the alarm/event has been noticed.

Uninitialized

Setting:

Uninitialized / Acknowledged / Unacknowledged

Alarm State

R

A discrete enumeration which gives an indication of whether

the alert is active and whether it has been reported.

Uninitialized

Setting:

Uninitialized

Clear - reported: Alarm not active and reported

Clear - not reported: Alarm not active and not reported

Active - reported: Alarm active and reported

Active - not reported: Alarm active and not reported

Time Stamp

R

The time when evaluation of the block was started and a

change in alarm/event state was detected that is unreported.

The time stamp value will be maintained constant until alert

confirmation has been received - even if another change of

state occurs.

Uninitialized

Setting:

MM / DD / YY (Month / Day / Year)

HH:MM:SS (Hour:Minute:Second)

Parameter

Parameter

Parameter

Parameter
Subelement

Access

Description and settings

Initial Value

.book Page 45 Tuesday, January 18, 2011 3:40 PM