Operation – KROHNE IFC 300 Converter FOUNDATION FIELDBUS EN User Manual

Page 25

background image

OPERATION

4

25

IFC 300

www.krohne.com

02/2011 - 4001086501 - AD IFC 300 FF R02 en

4.5.2 Manufacturer specific parameters of the signal converter for Transducer Block

Parameter

Parameter

Parameter

Parameter
Subelement

Access

Description and settings

Initial Value

CALIBRATION_C1_1

CALIBRATION_C1_1

CALIBRATION_C1_1

CALIBRATION_C1_1

Write Alarm

Write Alarm

Write Alarm

Write Alarm

Mix

Calibration (Fct. C1.1)

-

Zero_Point

R/W

Zero calibration (manual setting) (Fct. C1.1.1)

0.0

Setting:

-1.0…1.0

Size_Entry

R

Size entry (Fct. D2.4)

2

Setting:

1: value in [m] / 2: table [mm & inch]

Sensor_Size_Tab

R/W

Size (Fct. C1.1.2)

2000

Setting:

DN2.5…3000 [mm] 1/10"…120"

Sensor_Size_Val

R/W

Size (Fct. C1.1.2)

0.2

Setting:

0.0025…3.000 [m]

GK_Selection GK

R/W

GK selection (Fct. C1.1.3)

0

Setting:

0: GK & GKL / 1: GK / 2: GKL 3: GKH

GK_Value

R/W

GK (Fct. C1.1.4)

5.0

Setting:

0.5…12.0

GKL_Value

R/W

GKL (Fct. C1.1.5)

10.5

Setting:

0.5…20.0

GKH_Value

R/W

GKH (Fct. C1.1.6)

5.0

Setting:

0.5…12.0

Coil_Resist_Rsp

R/W

Coil resistance Rsp (Fct. C1.1.7)

60.0

Setting:

10.0…-220.0

Coil_Temp_Calc

R/W

Calibration coil temperature (Fct. C1.1.8)

293.15

Setting:

233.15…473.15

Density_Fact

R/W

Density (Fct. C1.1.9)

1000.0

Setting:

100.0…5000.0

EF_Electr_Fact

R/W

Calibrate electrode factor EF (Fct. C1.1.11) (manual setting)

0.003

Num_Electrodes

R/W

Number of electrodes (Fct. C1.1.12)

0

Field_Frequency

R/W

Field frequency (Fct. C1.1.13)

7

COLLECTION_

COLLECTION_

COLLECTION_

COLLECTION_

DIRECTORY

DIRECTORY

DIRECTORY

DIRECTORY

Collection Directory

Collection Directory

Collection Directory

Collection Directory

R

A directory that specifies the number, starting indices and DD

Item IDs of the data collections in each transducer within a

Transducer Block.

-

FILTER_C1_2

FILTER_C1_2

FILTER_C1_2

FILTER_C1_2

Write Alarm

Write Alarm

Write Alarm

Write Alarm

R/W

Filter (Fct. C1.2)

-

Limitation_Low

R/W

Limitation min process input (Fct. C1.2.1)

-12.0

Setting:

-100.000…-0.001

.book Page 25 Tuesday, January 18, 2011 3:40 PM