Operation – KROHNE IFC 300 Converter FOUNDATION FIELDBUS EN User Manual
Page 18
4
OPERATION
18
IFC 300
www.krohne.com
02/2011 - 4001086501 - AD IFC 300 FF R02 en
MEMORY_SUMMARY
Memory Summery
R
Summary of self diagnosis.
ok
Setting:
ok / bit 8…15 not used / EEPROM / FRAM / FLASH / ROM
application / ROM boot area / RAM ext / RAM int / Task Control
EEPROM_DIAG
EEPROM Diagnosis
R
Result of EEPROM self diagnosis.
ok
Setting:
ok / not supported action / unknown / busy / wait / first init /
changed / parameter error / page error / chip error / write
error / warning: inconsistent / warning: uncertain / warning:
write cycles / warning: one header / ok, page high
FRAM_DIAG
FRAM Diagnosis
R
Result of FRAM self diagnosis.
ok
Setting:
ok / not supported action / unknown / busy / wait / first init /
changed / parameter error / page error / chip error / write
error / warning: inconsistent / warning: uncertain / warning:
write cycles / warning: one header / ok, page high
workLOAD
R
Work load of the processor.
Current work load
DIAGNOSIS_BLK
DIAGNOSIS_BLK
DIAGNOSIS_BLK
DIAGNOSIS_BLK
Diagnosis Block
Diagnosis Block
Diagnosis Block
Diagnosis Block
R
Detailed diagnosis of the blocks.
-
RB_DIAG
RB Diagnosis
R
Setting:
Startup Device / MODE_BLK.ACTUAL is OOS / Memory
failure / Operating System / new : ID , DEV_TYPE , SNR / no
GDC Communication / Startup GDC , data invalid / Startup
Sensor , data valid / C-Number doesn't match to FF Software /
Hardware changed , C raw != C detected / Data Base doesn't
match to FF Software / MODE_BLK.PERMITTED doesn't
include Auto / MODE_BLK.TARGET is set OOS / GDC bold F
message / GDC F message / write from GDC to RB/TB doesn't
work / GDC Mfr unknown / GDC serial number / Boardinfo
incomplete or corrupt / action : write from GDC to RB/TB /
GDC W : no , M : no / GDC W : no , M : some /
GDC W : some , M : no / GDC W : no , M : all /
GDC W : all , M : no / GDC W : some , M : some /
GDC W : some , M : all / GDC W : all , M : some /
GDC Communication few loss / RS_STATE is not On-Line /
simulation active / unknown reason / Ok
Current diagnosis
TB_DIAG
TB Diagnosis
R
Setting:
Startup Device / RB : MODE_BLK.ACTUAL is OOS / Memory
failure / no GDC Communication / Startup GDC , data invalid /
Startup Sensor , data valid / Data Base doesn't match to FF
Software / MODE_BLK.PERMITTED doesn't include Auto /
MODE_BLK.TARGET is set OOS / GDC bold F message / GDC F
message / write from GDC to RB/TB doesn't work / Sensor
serial number / Sensor calibration date / GDC unit not
convertible to TB.prim_val / prim_val is outside range /
action : write from GDC to RB/TB / GDC Communication few
loss / no unit of GDC / GDC unit can't be converted to
TB.prim_range / a GDC value was not received / a GDC short
status is fatal or warn2 / PRIMARY_VALUE_1.status is
Uncertain / unknown reason / Ok
Current diagnosis
Parameter
Parameter
Parameter
Parameter
Subelement
Access
Description and settings
Initial Value
.book Page 18 Tuesday, January 18, 2011 3:40 PM