4
OPERATION
30
IFC 300
www.krohne.com
02/2011 - 4001086501 - AD IFC 300 FF R02 en
ST_REV
ST_REV
ST_REV
ST_REV
Static Revision
Static Revision
Static Revision
Static Revision
R
The revision level of the static data associated with the
function block. The revision value will be incremented each
time a static parameter value in the block is changed.
0
Setting:
0...65535
STRATEGY
STRATEGY
STRATEGY
STRATEGY
Strategy
Strategy
Strategy
Strategy
R/W
The strategy field can be used to identify grouping of blocks.
This data is not checked or processed by the block.
0 (=uninitialized)
Setting:
0...65535
TAG_DESC
TAG_DESC
TAG_DESC
TAG_DESC
Tag Description
Tag Description
Tag Description
Tag Description
R/W
This is the user description of the block useful for
documentation purpose. Not being updated frequently as it is
not being accessed by application.
spaces
Setting:
≤32 digits
ACK_OPTION
ACK_OPTION
ACK_OPTION
ACK_OPTION
Acknowledge
Acknowledge
Acknowledge
Acknowledge
Option
Option
Option
Option
R/W
Selection of whether alarms associated with the function
block will be automatically acknowledged.
Uninitialized
Setting:
Unack Alarm 1...15
ALARM_HYS
ALARM_HYS
ALARM_HYS
ALARM_HYS
Alarm Hysteresis
Alarm Hysteresis
Alarm Hysteresis
Alarm Hysteresis
R/W
Amount the PV must return within the alarm limits before the
alarm condition clears. Alarm Hysteresis is expressed as a
percent of the PV span.
0.05
Setting:
0...50%
ALARM_SUM
ALARM_SUM
ALARM_SUM
ALARM_SUM
Alarm Summary
Alarm Summary
Alarm Summary
Alarm Summary
Mix
The current alert status, unacknowledged states, unreported
states and disabled states of the alarms associated with the
function block.
-
Current
R
Setting:
HiHi Alarm / Hi Alarm / LoLo Alarm / Lo Alarm / Block Alarm
Uninitialized
Unacknowledged
R
Setting:
HiHi Alarm Unack / Hi Alarm Unack / LoLo Alarm Unack / Lo
Alarm Unack / Block Alarm Unack
Uninitialized
Unreported
R
Setting:
HiHi Alarm Unrep / Hi Alarm Unrep / LoLo Alarm Unrep / Lo
Alarm Unrep / Block Alarm Unrep
Uninitialized
Disabled
R
Setting:
HiHi Alarm Disabled / Hi Alarm Disabled / LoLo Alarm
Disabled / Lo Alarm Disabled / Block Alarm Disabled
Uninitialized
BLOCK_ALM
BLOCK_ALM
BLOCK_ALM
BLOCK_ALM
Block Alarm
Block Alarm
Block Alarm
Block Alarm
Mix
The block alarm is used for all configuration, hardware,
connection failure or system problems in the block. The cause
of the alert is entered in the subcode field. The first alert to
become active will set the "Active" status in the "Status"
attribute. As soon as the "Unreported" status is cleared by the
alert reporting task, another block alert may be reported
without clearing the "Active" status, if the subcode has
changed.
-
Unacknowledged
R/W
A discrete enumeration which is set to "Unacknowledged"
when an alarm occurs, and set to "Acknowledged" by a write
from a human interface device or other entity which can
acknowledge that the alarm/event has been noticed.
Uninitialized
Setting:
Uninitialized / Acknowledged / Unacknowledged
Alarm State
R
A discrete enumeration which gives an indication of whether
the alert is active and whether it has been reported.
Uninitialized
Setting:
Uninitialized / Clear - reported / Clear - not reported / Active -
reported / Active - not reported
Parameter
Parameter
Parameter
Parameter
Subelement
Access
Description and settings
Initial Value