OPERATION

4

27

IFC 300

www.krohne.com

02/2011 - 4001086501 - AD IFC 300 FF R02 en

PRIMARY_VALUE_1_

PRIMARY_VALUE_1_

PRIMARY_VALUE_1_

PRIMARY_VALUE_1_

RANGE

RANGE

RANGE

RANGE

Primary Value 1 Range

Primary Value 1 Range

Primary Value 1 Range

Primary Value 1 Range

R

The high and low range limit values, the engineering units

code and the number of digits to the right of the decimal point

to be used to display the Primary Value.

-

EU_100

Engineering Unit 100

R

The engineering unit value which represents the upper end of

range of the associated Block Parameter.

-

EU_0

Engineering Unit 0

R

The engineering unit value which represents the lower end of

range of the associated Block Parameter.

-

UNITS_INDEX

Inits Index

R

Device Description units code index for the engineering unit

descriptor for the associated block value.

-

DECIMAL

Decimal (Point)

R

The number of digits to the right of the decimal point which

should be used by an interface device in displaying the

specified parameter.

0

Setting:

0...255

SELF_TEST_C1_3

SELF_TEST_C1_3

SELF_TEST_C1_3

SELF_TEST_C1_3

R/W

Self test (Fct. C1.3)

-

Empty_Pipe

R/W

empty pipe detect (Fct. C1.3.1)

0

Setting:

0: off / 1: conductivity / 2: cond. & empty pipe (S) / 3: cond. &

empty pipe (F)

Limit_Empty_Pipe

R/W

limit empty pipe (Fct. C1.3.2)

0.006

Setting:

0.0…0.9999

Full_Pipe

R/W

full pipe detect (Fct. C1.3.4)

0

Setting:

0: off / 1: on

Limit_Full_Pipe

R/W

limit full pipe (Fct. C1.3.5)

0.006

Setting:

0.0…0.9999

Linearity

R/W

linearity (Fct. C1.3.6)

0

Setting:

0: off / 1: on

Gain

R/W

gain (Fct. C1.3.8)

0

Setting:

0: off / 1: on

Coil_Current

R/W

coil current (Fct. C1.3.0)

0

Setting:

0: off / 1: on

Flow_Profile

R/W

flow profile (Fct. C1.3.10)

0

Setting:

0: off / 1: on

LimitFlowProfile

R/W

limit flow profile (Fct. C1.3.11)

0

Setting:

0: off / 1: on

Electrode_Noise

R/W

electrode noise (Fct. C1.3.13)

0

Setting:

0: off / 1: on

LimitElectrNoise

R/W

limit electrode noise (Fct. C1.3.14)

0.1

Setting:

0.0...12.0

Parameter

Parameter

Parameter

Parameter
Subelement

Access

Description and settings

Initial Value