Operation – KROHNE IFC 300 Converter FOUNDATION FIELDBUS EN User Manual

Page 33

background image

OPERATION

4

33

IFC 300

www.krohne.com

02/2011 - 4001086501 - AD IFC 300 FF R02 en

LO_LO_ALM

LO_LO_ALM

LO_LO_ALM

LO_LO_ALM

Low Low Alarm

Low Low Alarm

Low Low Alarm

Low Low Alarm

Mix

The status for Low Low Alarm and its associated time stamp.

Settings of 5 subelements see in the following part.

-

Settings of 5 subelements for previous 2 parameters Low Alarm and Low Low Alarm:

Unacknowledged

R/W

Setting:

Uninitialized / Acknowledged / Unacknowledged

Uninitialized

Alarm State

R

Setting:

Uninitialized / Clear - reported / Clear - not reported / Active -

reported / Active - not reported

Uninitialized

Time Stamp

R

Setting:

MM / DD / YY (Month / Day / Year)

HH:MM:SS (Hour:Minute:Second)

Uninitialized

Subcode

R

Setting:

Other / Block Configuration / Link Configuration / Simulation

Active / Local Override / Device Fault State / Device

Maintenance / Input Failure / Output Failure / Memory

Failure / Lost Static Data / Lost NV Data / Readback Check /

Maintenance Needed / Power Up / Out Of Service

Other

Value

R

A numerical quantity entered by a user or calculated by the

algorithm.

0.0

LO_LIM

LO_LIM

LO_LIM

LO_LIM

Low Limit

Low Limit

Low Limit

Low Limit

R/W

The setting for Low Alarm in engineering units.

Setting range see in the following part.

0

LO_LO_LIM

LO_LO_LIM

LO_LO_LIM

LO_LO_LIM

Low Low Limit

Low Low Limit

Low Low Limit

Low Low Limit

R/W

The setting for Low Low Alarm in engineering units.

Setting range see in the following part.

0

LO_PRI

LO_PRI

LO_PRI

LO_PRI

Low Priority

Low Priority

Low Priority

Low Priority

R/W

Priority of the Low Alarm.

Setting see in the following part.

1

LO_LO_PRI

LO_LO_PRI

LO_LO_PRI

LO_LO_PRI

Low Low Priority

Low Low Priority

Low Low Priority

Low Low Priority

R/W

Priority of the Low Low Alarm.

Setting see in the following part.

1

Setting range for previous 2

parameters:

x_y_LIM

x_y_Limit

-3.39 E38…+3.39 E38 / - INF (- infinite) / + INF (+ infinite)

Setting for previous 2

parameters:

x_y_PRI

x_y_Priority

0: The associated alert may clear when the priority is changed

to 0, but it will never occur.

1: The associated alert is not send as a notification. If the

priority is above 1, then the alert must be reported.

2: Reserved for alerts that do not require the attention of a

plant operator, e.g. diagnostic and system alerts. Block alarm,

error alarm and update event have a fixed priority of 2.

3...7: Increasing higher priorities - advisory alarms.

8...15: Increasing higher priorities - critical alarms.

0

LOW_CUT

LOW_CUT

LOW_CUT

LOW_CUT

Low Cutoff

Low Cutoff

Low Cutoff

Low Cutoff

R/W

Limit used in square root processing. A value of zero percent

of scale is used in block processing if the transducer value

falls below this limit, in %of scale. This feature may be used to

eliminate noise near zero for a flow sensor.

0

Setting:

≥0.0

OUT

OUT

OUT

OUT

Output

Output

Output

Output

R/W

The primary analog discrete value calculated as a result of

executing the function.

Note:

Note:

Note:

Note:

W = Writeable only by setting "OOS" in MODE_BLK

-

Status

R

Actual Status is displayed.

-

Value

R/W

Actual Value

-

Parameter

Parameter

Parameter

Parameter
Subelement

Access

Description and settings

Initial Value

.book Page 33 Tuesday, January 18, 2011 3:40 PM