Operation – KROHNE IFC 300 Converter FOUNDATION FIELDBUS EN User Manual
Page 33
OPERATION
4
33
IFC 300
www.krohne.com
02/2011 - 4001086501 - AD IFC 300 FF R02 en
LO_LO_ALM
LO_LO_ALM
LO_LO_ALM
LO_LO_ALM
Low Low Alarm
Low Low Alarm
Low Low Alarm
Low Low Alarm
Mix
The status for Low Low Alarm and its associated time stamp.
Settings of 5 subelements see in the following part.
-
Settings of 5 subelements for previous 2 parameters Low Alarm and Low Low Alarm:
Unacknowledged
R/W
Setting:
Uninitialized / Acknowledged / Unacknowledged
Uninitialized
Alarm State
R
Setting:
Uninitialized / Clear - reported / Clear - not reported / Active -
reported / Active - not reported
Uninitialized
Time Stamp
R
Setting:
MM / DD / YY (Month / Day / Year)
HH:MM:SS (Hour:Minute:Second)
Uninitialized
Subcode
R
Setting:
Other / Block Configuration / Link Configuration / Simulation
Active / Local Override / Device Fault State / Device
Maintenance / Input Failure / Output Failure / Memory
Failure / Lost Static Data / Lost NV Data / Readback Check /
Maintenance Needed / Power Up / Out Of Service
Other
Value
R
A numerical quantity entered by a user or calculated by the
algorithm.
0.0
LO_LIM
LO_LIM
LO_LIM
LO_LIM
Low Limit
Low Limit
Low Limit
Low Limit
R/W
The setting for Low Alarm in engineering units.
Setting range see in the following part.
0
LO_LO_LIM
LO_LO_LIM
LO_LO_LIM
LO_LO_LIM
Low Low Limit
Low Low Limit
Low Low Limit
Low Low Limit
R/W
The setting for Low Low Alarm in engineering units.
Setting range see in the following part.
0
LO_PRI
LO_PRI
LO_PRI
LO_PRI
Low Priority
Low Priority
Low Priority
Low Priority
R/W
Priority of the Low Alarm.
Setting see in the following part.
1
LO_LO_PRI
LO_LO_PRI
LO_LO_PRI
LO_LO_PRI
Low Low Priority
Low Low Priority
Low Low Priority
Low Low Priority
R/W
Priority of the Low Low Alarm.
Setting see in the following part.
1
Setting range for previous 2
parameters:
x_y_LIM
x_y_Limit
-3.39 E38…+3.39 E38 / - INF (- infinite) / + INF (+ infinite)
Setting for previous 2
parameters:
x_y_PRI
x_y_Priority
0: The associated alert may clear when the priority is changed
to 0, but it will never occur.
1: The associated alert is not send as a notification. If the
priority is above 1, then the alert must be reported.
2: Reserved for alerts that do not require the attention of a
plant operator, e.g. diagnostic and system alerts. Block alarm,
error alarm and update event have a fixed priority of 2.
3...7: Increasing higher priorities - advisory alarms.
8...15: Increasing higher priorities - critical alarms.
0
LOW_CUT
LOW_CUT
LOW_CUT
LOW_CUT
Low Cutoff
Low Cutoff
Low Cutoff
Low Cutoff
R/W
Limit used in square root processing. A value of zero percent
of scale is used in block processing if the transducer value
falls below this limit, in %of scale. This feature may be used to
eliminate noise near zero for a flow sensor.
0
Setting:
≥0.0
OUT
OUT
OUT
OUT
Output
Output
Output
Output
R/W
The primary analog discrete value calculated as a result of
executing the function.
Note:
Note:
Note:
Note:
W = Writeable only by setting "OOS" in MODE_BLK
-
Status
R
Actual Status is displayed.
-
Value
R/W
Actual Value
-
Parameter
Parameter
Parameter
Parameter
Subelement
Access
Description and settings
Initial Value
.book Page 33 Tuesday, January 18, 2011 3:40 PM