Operation – KROHNE IFC 300 Converter FOUNDATION FIELDBUS EN User Manual
Page 12
4
OPERATION
12
IFC 300
www.krohne.com
02/2011 - 4001086501 - AD IFC 300 FF R02 en
NORMAL
Normal
R/W
This is the mode which the block should be set to during
normal operating conditions.
Auto
Setting:
Auto / OOS
ST_REV
ST_REV
ST_REV
ST_REV
Static Revision
Static Revision
Static Revision
Static Revision
R
The revision level of the static data associated with the
function block. The revision value will be incremented each
time a static parameter value in the block is changed.
0
Setting:
0...65535
STRATEGY
STRATEGY
STRATEGY
STRATEGY
Strategy
Strategy
Strategy
Strategy
R/W
The strategy field can be used to identify grouping of blocks.
This data is not checked or processed by the block.
0 (=uninitialized)
Setting:
0...65535
TAG_DESC
TAG_DESC
TAG_DESC
TAG_DESC
Tag Description
Tag Description
Tag Description
Tag Description
R/W
The user description of the intended application of the block.
spaces
Setting:
≤32 digits
ACK_OPTION
ACK_OPTION
ACK_OPTION
ACK_OPTION
Acknowledge Option
Acknowledge Option
Acknowledge Option
Acknowledge Option
R/W
Selection of whether alarms associated with the function
block will be automatically acknowledged.
Uninitialized
Setting:
Disc Alm Disabled / Block Alm Disabled
ALARM_SUM
ALARM_SUM
ALARM_SUM
ALARM_SUM
Alarm Summary
Alarm Summary
Alarm Summary
Alarm Summary
R
The current alert status, unacknowledged states, unreported
states and disabled states of the alarms associated with the
function block.
Uninitialized
Current
R
The active status of each alarm. The zero (0) state will be used
to indicate alarm clear.
0
Unacknowledged
R
Setting:
Disc Alm Unack / Block Alm Unack
Uninitialized
Unreported
R
Setting:
Disc Alm Unrep / Block Alm Unrep
Uninitialized
Disabled
R/W
Setting:
Disc Alm Disabled / Block Alm Disabled
Uninitialized
BLOCK_ALM
BLOCK_ALM
BLOCK_ALM
BLOCK_ALM
Block Alarm
Block Alarm
Block Alarm
Block Alarm
Mix
The block alarm is used for all configuration, hardware,
connection failure or system problems in the block. The cause
of the alert is entered in the subcode field. The first alert to
become active will set the "Active" status in the "Status"
attribute. As soon as the "Unreported" status is cleared by the
alert reporting task, another block alert may be reported
without clearing the "Active" status, if the subcode has
changed.
-
Unacknowledged
R/W
A discrete enumeration which is set to "Unacknowledged"
when an alarm occurs, and set to "Acknowledged" by a write
from a human interface device or other entity which can
acknowledge that the alarm/event has been noticed.
Uninitialized
Setting:
Uninitialized / Acknowledged / Unacknowledged
Alarm State
R
A discrete enumeration which gives an indication of whether
the alert is active and whether it has been reported.
Uninitialized
Setting:
Uninitialized / Clear - reported / Clear - not reported / Active -
reported / Active - not reported
Parameter
Parameter
Parameter
Parameter
Subelement
Access
Description and settings
Initial Value
.book Page 12 Tuesday, January 18, 2011 3:40 PM