beautypg.com

Electrical connections, 10 interface cable – KROHNE IFC 300 Converter Quickstart EN User Manual

Page 49

background image

ELECTRICAL CONNECTIONS

3

49

IFC 300

www.krohne.com

08/2010 - 4000070303 - QS IFC 300 R06 en

3.6.10 Interface cable

The data interface cable is a shielded, 3 x 1.5 mm

2

LIYCY cable. The standard length 10 m /

32.8 ft is included in the delivery.

1 Strip the conductor to dimension a.
2 Trim the outer shield to dimension b and pull it over the outer sheath.
3 Crimp the wire end ferrules onto the conductors 1, 2 and 3.

Connect the shielding at both sides of the cable via the special cable gland.

Preparing the interface cable

Figure 3-33: Preparing the interface cable

a = 100 mm / 4"
b = 10 mm / 0.4"

Connecting shielding via special cable gland

Figure 3-34: Connecting the shield within the cable gland

1 Wires
2 Isolation
3 Shielding
4 Isolation
5 Feed cable through dome nut and clamping insert and fold shielding over clamping insert. Make sure that the braided

shield overlaps the O-ring by 2 mm / 3/32".

6 Push clamping insert into body.
7 Tighten the dome nut.