ELECTRICAL CONNECTIONS

3

31

IFC 300

www.krohne.com

08/2010 - 4000070303 - QS IFC 300 R06 en

3.5.1 Connecting the signal and field current cables, field housing

• The outer shield of signal cable A and/or B is connected electrically with the housing via the

clip of the strain relief.

• If a shielded field current cable is used, the shield must NOT

NOT

NOT

NOT be connected in the housing of

the signal converter.

• Bending radius: ≥ 50 mm / 2"

1 Remove the locking screw and open the housing cover.
2 Pass the prepared signal and field current cables through the cable entries and connect the

corresponding stranded drain wires and conductors.

3 Secure the field current cable using the clip. Any shield that is present must NOT

NOT

NOT

NOT be connect-

ed.

4 Secure the signal cable using the clip. This also connects the outer shield to the housing.
5 Close the housing cover and secure it with the locking screw.

Figure 3-13: Electrical connection of the signal and field current cables, field housing

INFORMATION!
Each time a housing cover is opened, the thread should be cleaned and greased. Use only resin-
free and acid-free grease.
Ensure that the housing gasket is properly fitted, clean and undamaged.