beautypg.com

Electrical connections – KROHNE IFC 300 Converter Quickstart EN User Manual

Page 18

background image

3

ELECTRICAL CONNECTIONS

18

IFC 300

www.krohne.com

08/2010 - 4000070303 - QS IFC 300 R06 en

3.4.2 Preparing signal cable A, connection to signal converter

Field housing

• The outside shield (60) is connected in the field housing directly via the shield and a clip.
• Bending radius: ≥ 50 mm / 2"

Required materials:

• PVC insulation tubing, Ø2.5 mm / 0.1"
• Heat-shrinkable tubing
• Wire end ferrule to DIN 46 228: E 1.5-8 for the stranded drain wire (1)
• 2x wire end ferrules to DIN 46 228: E 0.5-8 for the insulated conductors (2, 3)

1 Strip the conductor to dimension a.

Trim the outer shield to dimension b and pull it over the outer sheath.

2 Cut off the inner shield (10) and the stranded drain wire (6). Make sure not to damage the

stranded drain wire (1).

3 Slide an insulating tube over the stranded drain wire (1).
4 Crimp the wire end ferrules onto the conductors (2, 3) and stranded drain wire.
5 Pull the heat-shrinkable tubing over the prepared signal cable.

INFORMATION!
Assembly materials and tools are not part of the delivery. Use the assembly materials and tools
in compliance with the applicable occupational health and safety directives.

Figure 3-2: Signal cable A, preparation for field housing

a = 80 mm / 3.15"
b = 10 mm / 0.39"