beautypg.com

Electrical connections – KROHNE IFC 300 Converter Quickstart EN User Manual

Page 35

background image

ELECTRICAL CONNECTIONS

3

35

IFC 300

www.krohne.com

08/2010 - 4000070303 - QS IFC 300 R06 en

3.5.5 Connection diagram for measuring sensor, field housing

• If a shielded field current cable is used, the shield must NOT

NOT

NOT

NOT be connected in the housing of

the signal converter.

• The outer shield of signal cable A or B in the signal converter housing is connected via the

strain relief terminal.

• Bending radius of signal and field current cable: ≥ 50 mm / 2"
• The following illustration is schematic. The positions of the electrical connection terminals

may vary depending on the housing version.

DANGER!
The device must be grounded in accordance with regulations in order to protect personnel
against electric shocks.

Figure 3-19: Connection diagram for measuring sensor, field housing

1 Electrical terminal compartment in housing of the signal converter for signal and field current cable.
2 Signal cable A
3 Signal cable B
4 Field current cable C
5 Connection box of measuring sensor
6 Functional ground FE