13.2 Troubleshooting table for general errors

Warning
Maintenance may only be performed by a qualified service and maintenance engineer.

General errors

Symptom

Cause

Solution

Remark

Gas smell

Gas leak

Warning
Close the main gas valve immediately.
Warning
Do not operate any switches.
Warning
No naked flames.
Warning
Ventilate the boiler room.

Warning
Contact your installation engineer or local gas company

immediately.

Display is off

Appliance is turned off

Start the appliance up

(9 "Starting and running")

No supply voltage

present

1. Check if the isolator is ON.
2. Check that there is power to the isolator.
3. Check whether the ON/OFF switch of the electronic controller is

ON (position I).

4. Check whether there is power to the electrical connector block.
5. The measured voltage must be 230 VAC (-15%, +10%).

See the SGS electrical diagram

(17 "Appendices")

If the error persists, consult your installation engineer.

Defective fuse(s)

Replace fuse(s)

To replace the fuses, you must contact your installation engineer.