Troubleshooting table for general errors, 2 "troubleshooting table for general, Errors") – A.O. Smith 30 User Manual
Page 80: Display

is
Instruction manual SGS
80
13.2 Troubleshooting table for general errors
Warning
Maintenance may only be performed by a qualified service and maintenance engineer.
General errors
Symptom
Cause
Solution
Remark
Gas smell
Gas leak
Warning
Close the main gas valve immediately.
Warning
Do not operate any switches.
Warning
No naked flames.
Warning
Ventilate the boiler room.
Warning
Contact your installation engineer or local gas company
immediately.
Display is off
Appliance is turned off
Start the appliance up
No supply voltage
present
1. Check if the isolator is ON.
2. Check that there is power to the isolator.
3. Check whether the ON/OFF switch of the electronic controller is
ON (position I).
4. Check whether there is power to the electrical connector block.
5. The measured voltage must be 230 VAC (-15%, +10%).
See the SGS electrical diagram
If the error persists, consult your installation engineer.
Defective fuse(s)
Replace fuse(s)
To replace the fuses, you must contact your installation engineer.