M72 - M73 - M74 - M75

EN - 40

6. TECHNICAL SPECIFICATIONS

Accuracy is indicated as [%reading + (digit number*resolution)] at: 23°C±5°C, <70%HR.

DC/AC TRMS Voltage

Range Resolution

Accuracy

DC

Accuracy

(30

70Hz)

Accuracy

(70

400Hz)

Input

impedance

1.0

 999.9mV

0.1mV

(0.5rdg+2dgt) (1.0rdg+2dgt) (2.0rdg+2dgt) 1M

1.000

 9.999V

0.001V

10.00

 99.99V

0.01V

100.0

 605.0V

0.1V

MAX, MIN, AVG, PEAK, resolution:

(5.0% rdg + 10 dgt); responce time: 500ms (MAX, MIN, AVG),1ms (PEAK)

Max crest factor: 3.0: V<1.0V; 1.5: V≥1.0V

DC/AC TRMS Current (with external jaws)

Range Resolution

Accuracy

DC

Accuracy

(30

70Hz)

Accuracy

(70

400Hz)

Input

impedance

Overload

protection

1.0

 999.9mV

0.1mV

(0.5rdg+

2dgt)

(1.0 rdg +

2 dgt)

(2.0 rdg +

2 dgt)

1M

605V AC

max RMS

1.000

 1.200V

0.001V

NOTE The mentioned accuracy does not consider the transducer's accuracy. Please refer to its user's manual
MAX, MIN, AVG, PEAK, resolution:

(5.0% rdg + 10 dgt); responce time: 500ms (MAX, MIN, AVG),1ms (PEAK)

Minimum input current: 1mV x transduction ratio of the clamp
Max crest factor: 3.0: V<1.0V; 1.5: V≥1.0V

Frequency measurement with test leads

Range Resolution

Accuracy

Input

impedance

30.0

 199.9Hz

0.1Hz

(0.5rdg + 2dgt)

1M

200

 400Hz

1Hz

Input voltage: 1mV

 605.0V

Frequency measurement with jaws

Range Resolution

Accuracy

Overload

protection

30.0

 199.9Hz

0.1Hz

(0.5rdg + 2dgt)

605V AC max RMS

200

 400Hz

1Hz

Input voltage: 1mV

 1V

Resistance and continuity test

Range Resolution

Accuracy

Buzzer Overload

protection

0.00

 39.99  0.01

(1.0%rdg + 5dgt)

R<40

 605V AC max RMS for 1 minute

40.0

 399.9  0.1

400

 3999 

1

4.00

 39.99 k 10


Phase sequence and phase conformity

Measuring method

Working voltage (V)

System

1 test lead (1W)

90

 315 (Phase - Ground)

up to 315 V (Phase - Ground)

up to 550V (Phase - Phase)

2 test leads (2W)

90

 315 (Phase - Neutral)

up to 315 V (Phase - Neutral)

up to 550V (Phase - Phase) (*)

Max crest factor: 1.5 ; Frequency range: 45

 65 Hz

(*) The two-wire measurement can be performed also phase to phase in plants without neutral, even with one phase to earth, but

always with phase to phase voltage up to 550V

0.2A: Continuity with 200mA (M72, M74, M75)

Range Resolution

Accuracy

Overload

protection

0.00

 19.99 0.01

(5.0% rdg + 3 dgt)

605V max RMS

20.0

 99.9

0.1

Test current: >200mA DC up to 5

 (measuring cables resistance included)

Accuracy of current measurement: 1mA
Open circuit voltage: 4 < V

0

< 24V