M72 - M73 - M74 - M75

EN - 19

CAUTION

During measurement:
GO must be always kept pressed or its surface must be always touched

(only for mode 1W)

 The test probe, except for the phase cable under test, must not be in touch

or close to any voltage source which may block the measurement due to
the instrument’s sensitivity

 The test probe must be kept in touch with the phase cable.

15. At the end of the test, if two tested

cables are in a correct phase sequenze,
the instrument emits a double sound to
signal the positive outcome of the test
and displays a screen like this

Correct phase
sequence

Phase rotation

16. At the end of the test, if two cables

belong to the same phase, the
instrument emits a double sound to
sigla the positive outcome of the test
and displays a screen like this

Cables belonging to
the same phase

Compliance between
one cable and
another

17. At the end of the test, if two tested

cables are not in the correct phase
sequenze, the instrument emits a
prolonged sound to signal the negative
outcome of the test and displays a
screen like this

Wrong phase
sequence

Phase rotation

18. To perform a new measurement press GO, then re-start from point 6

CAUTION

Although two cables are in sequence it doesn’t mean that the third cable is in
sequence too. It’s not excluded that the cabling was made by mistake with a
double phase cable. To clear any possible doubt always perform at least two
measurements by testing the cables two by two.