beautypg.com

HT instruments М75 User Manual

Page 38

background image

M72 - M73 - M74 - M75

EN - 36

4. If during measurement an excessive

contact voltage is detected (higher than
50V) the instrument does not perform the
test and emits a prolonged sound to
signal the anomalous situation. The
screen beside is displayed for 5 seconds
after which the instrument displays the
default screen of Ra test

5. The instrument dispalys the

symbol

when:

The instrument is operating in a

critical situation as for example in
presence of overvoltages

The instrument cannot guarantee the

measuring uncertainty lower than
30% of the reading, according to
IEC/EN61557-1


6. If during measurement the green probe is

connected to the phase conductor and
the black probe is connected to the
protective conductor, the instrument does
not perform the test and emits a
prolonged sound to signal the anomalous
situation. The screen beside is displayed
for 5 seconds after which the instrument
displays the default screen of Ra test.
This can happen even if the wrong
connection is performed on the back side
of the power socket















This manual is related to the following products: