As in, Table 5-1, Loop style – Fire-Lite PS-Tools MS-9200UDLS User Manual
Page 42: Day light savings
Configuring Fire Panels
34
198 Pt Addr. Panel
PS-Tools
08/2010
Note
•
If the Canadian option is enabled, then the silence inhibit for NACs becomes a
“global” option. That is, in the panel if you change any NAC to silence inhibit, the
remaining NACs change to silence inhibit. Similarly, if you set any one NAC to
no silence inhibit all the NACs silence inhibit is turned off.
•
When importing a customer database file from the previous version of PS-Tools,
a check must be performed to ensure whether the Canadian option is enabled. If
the Canadian option is enabled, then the NAC’s silence inhibit must be checked.
If either of them is enabled, then all the NAC’s silence inhibit must be turned off,
and a corresponding message must be displayed to the user.
•
If the Canadian option is ON, then the PAS and Pre-signal timers must be set to 0
and no editing is allowed.
Table 5-1
Module types blocked from selection
Changes to
Monitor
Pull Station
MON User defined 3
Pull Station
Medical Alert, Hazard Alert, and Tornado Alert
Supervisory
Supervisory AR (Non-Latching)
Supervisory
MON User defined 7, 8, 9, 13, 16, and 17
Supervisory
Drill Switch AR (Non-Latching)
Drill Switch
Process Monitor AR and Process Monitor
Supervisory
Module and Zone types available for Canadian option
Loop Style
In Loop 1, select the wiring style for the loop. The wiring style can be Style 4 or Style 6. The default
wiring type is Style 4.
Day Light Savings
To configure the Day Light Savings feature
1.
Select the starting day and month in the Daylight Savings Time Starts list.
Zone types blocked from selection
Changes to
AR(auto-resettable) Supervisory
Supervisory
Drill Switch AR
Drill Switch
Process monitor, hazard, tornado, and medical alert
Supervisory