Timers – Fire-Lite PS-Tools MS-9200UDLS User Manual
Page 40
Configuring Fire Panels
32
198 Pt Addr. Panel
PS-Tools
08/2010
Figure 5-5
Configuring System Setup Options
Timers
You can program the fire panel for PAS or Presignal operation, not both. If you set the PAS Delay
timer with a value greater than 000, and then set the Presignal Delay timer with a value greater than
000, the PAS Delay timer is automatically reset to 000. Only one of the two timers can have a delay
time set.
To configure the timers
1.
Select a Positive Alarm Sequence Delay of 001 to 180 seconds for all devices programmed for
PAS. The factory default setting is 000 for no delay.
2.
Select a Alarm Presignal Delay of 001 to 180 seconds for all devices programmed for
Presignal. The factory default setting is 000 for no delay.
3.
Select a Waterflow Retard of 01 to 90 seconds for all devices programmed for Waterflow
delay. The factory default setting for Waterflow delay is 000 for no delay. A delay can be added
prior to declaring a waterflow type of alarm.
Note
Ensure to include the built-in delays of the waterflow device.
4.
You can delay the reporting of an AC power loss to a central station by setting the length of the
desired delay. Type the AC Loss Delay in hours (00 to 23 hour delay). The factory default
setting is 02 hours (see