Alarm and trouble activation, Configuration appendix c: ms-9600, Table 17 sw3 settings for alarm/trouble - zones – Fire-Lite ACM-8RF Control Relay Module User Manual
Page 41

Configuration
Appendix C: MS-9600
ACM-8RF PN 50362:C 03/21/01
41
Alarm and Trouble Activation
When “Alarm/Trouble” is selected, relays 1 - 4 respond to alarm signals and
relays 5 - 8 respond to trouble signals.
The following table displays an example of how to set the DIP switches on four
(4) ACM-8RFs to annunciate the zones of an annunciator address. Although
this table shows System Points & Zones 1 to 8 (address 01), by referring to Table
13 on page 38 it can be determined which ACM-8RF will activate what zone
or point, depending on the address that is set on the rotary switches.
Table 17 SW3 Settings for Alarm/Trouble - Zones
Note: If the System Points (system alarm, trouble or silence etc.) is not required, up to
fourteen (14) ACM-8RFs may be used to allow activation of FACP zones 1 through 56.
When using this configuration do not use the DIP Switch settings for the 1st ACM-8RF.
ACM-8RF
Alarm Relay
MS-9600 Zone
ACM-8RF
Trouble Relay
MS-9600 Zone
1st ACM-8RF
SW3-1 = ON
SW3-5 = ON
All others = OFF
1=System Alarm
System Point
5=System Trouble
System Point
2 (not used)
System Point
Relay 6 (not used)
System Point
3 (not used)
System Point
7=System Off Normal
System Point
4 (not used)
System Point
8=System Supervisory
System Point
2nd ACM-8RF
SW3-2 = ON
SW3-5 = ON
All others = OFF
1 (not used)
System Point
5=NAC Fault
System Point
2 (not used)
System Point
6=Walktest Start
System Point
3 (not used)
System Point
7=Battery Fail
System Point
4 (not used)
System Point
8=AC Fail
System Point
3rd ACM-8RF
SW3-3 = ON
SW3-5 = ON
All others = OFF
Relay 1
Zone 1
Relay 5
Zone 1
Relay 2
Zone 2
Relay 6
Zone 2
Relay 3
Zone 3
Relay 7
Zone 3
Relay 4
Zone 4
Relay 8
Zone 4
4th ACM-8RF
SW3-4 = ON
SW3-5 = ON
All others = OFF
Relay 1
Zone 5
Relay 5
Zone 5
Relay 2
Zone 6
Relay 6
Zone 6
Relay 3
Zone 7
Relay 7
Zone 7
Relay 4
Zone 8
Relay 8
Zone 8