Application example #3 – Fire-Lite ACM-8RF Control Relay Module User Manual
Page 26

Appendix A: MS-5210UD
Application Example #3
26
ACM-8RF PN 50362:C 03/21/01
Application Example #3
Two LED-10 Annunciators and 10 Alarm Only Relays
(no system status relays)
Program the MS-5210UD at Level 3 addresses 02 - 03 for the proper address
setting. The address selected must be the highest or maximum address value
selected on any annunciator or ACM-8RF connected to the EIA-485 port.
(Refer to the Programming Section of the MS-5210UD Instruction Manual).
For this example, only one relay per MS-5210UD zone is required and the
ACM-8RFs are sharing the EIA-485 bus with two LED-10s. Since ACM-8RFs
are sharing the bus with two other devices, the address setting for the ACM-
8RFs should be switches SW1 = 0 and SW2 = 3. Enter this address into the
MS-5210UD Level 3 addresses 02 - 03.
Since each ACM-8RF module contains eight relays, two ACM-8RF modules
are required for 10 zones. Refer to the following chart for switch settings:
Table 8 Settings for Zone Alarm Activation with LED-10s
MS-5210UD
Zone
ACM-8RF
Relay
Switch Settings
Z1
Relay 1
1st ACM-8RF
SW1=0; SW2=3 (Address ‘03’)
SW3-2 = ON; SW3-5 = ON
All other SW3s = OFF
SW4-1=ON; SW4-2=ON
Z2
Relay 2
Z3
Relay 3
Z4
Relay 4
Z5
Relay 5
Z6
Relay 6
Z7
Relay 7
Z8
Relay 8
Z9
Relay 1
2nd ACM-8RF
SW1=0, SW2=3 (Address ‘03’)
SW3-3 = ON; SW3-5 = ON
All other SW3s = OFF
SW4-1=ON; SW4-2=OFF
Z10
Relay 2
n/a
Relay 3
n/a
Relay 4
n/a
Relay 5
n/a
Relay 6
n/a
Relay 7
n/a
Relay 8