Application example #1 – Fire-Lite ACM-8RF Control Relay Module User Manual
Page 24
Appendix A: MS-5210UD
Application Example #1
24
ACM-8RF PN 50362:C 03/21/01
Application Example #1
Zone Alarm Only Activation (no system status relays)
Program the MS-5210UD at Level 3 addresses 02 - 03 for the proper address
setting. The address selected must be the highest or maximum address value
selected on any annunciator or ACM-8RF connected to the EIA-485 port.
(Refer to the Programming Section of the MS-5210UD Instruction Manual).
For this example, only one relay per zone is required and the ACM-8RFs are
the only devices on the EIA-485 bus. Since only ACM-8RFs occupy the bus,
the address setting for them should be switch SW1 = 0 and switch SW2 = 1.
Enter this address into the MS-5210UD Level 3 addresses 02 - 03.
Since each ACM-8RF module contains eight relays, two ACM-8RF modules
are required for 10 zones. Refer to the following chart for switch settings:
Table 6 Settings for Zone Alarm Activation
MS-5210UD
Zone
ACM-8RF
Relay
Switch Settings
Z1
Relay 1
1st ACM-8RF
SW1=0; SW2=1 (Address ‘01’)
SW3-2 = ON; SW3-5 = ON
All other SW3s = OFF
SW4-1=ON; SW4-2=ON
Z2
Relay 2
Z3
Relay 3
Z4
Relay 4
Z5
Relay 5
Z6
Relay 6
Z7
Relay 7
Z8
Relay 8
Z9
Relay 1
2nd ACM-8RF
SW1=0, SW2=1 (Address ‘01’)
SW3-3 = ON; SW3-5 = ON
All other SW3s = OFF
SW4-1=ON; SW4-2=OFF
Z10
Relay 2
n/a
Relay 3
n/a
Relay 4
n/a
Relay 5
n/a
Relay 6
n/a
Relay 7
n/a
Relay 8