Configuration, Setting rotary switches – Fire-Lite ACM-8RF Control Relay Module User Manual
Page 38

Appendix C: MS-9600
Configuration
38
ACM-8RF PN 50362:C 03/21/01
Configuration
Setting Rotary Switches
The Address Select Rotary Switches (SW1 & SW2) are used to determine
which FACP annunciator address will trigger relays on the ACM-8RF. Use the
following table to set these switches. Refer to "Address Switches - SW1 and
SW2" on page 15 for information on setting these switches.
M = Module D = Detector
Table 13 SW1 & SW2 Switch Settings
Note: If a UDACT-F is installed and selected in control panel programming, it will
automatically assign addresses 20 - 31 to the UDACT-F and disable the selection of
these addresses.
FACP
Address
SW1
SW2
Relay Activation for:
1
0
1
8 System Points & Zones 1-56
2
0
2
Zones 57-99 & 2 NACs
3
0
3
Loop 1, Address M1 - M64
4
0
4
Loop 2, Address M1 - M64
5
0
5
Loop 1, Address M65 - M128
6
0
6
Loop 2, Address M65 - M128
7
0
7
Loop 1, Address M129 - M159 &
Loop 2, Address M129 - M159
8
0
8
Loop 1, Address D1 - D64
9
0
9
Loop 2, Address D1 - D64
10
1
0
Loop 1, Address D65 - D128
11
1
1
Loop 2, Address D65 - D128
12
1
2
Loop 1, Address D129 - D159 &
Loop 2, Address D129 - D159
13 - 19
Not Used
20
2
0
8 System Points & Zones 1-56
21
2
1
Zones 57-99 & 2 NACs
22
2
2
Loop 1, Address M1 - M64
23
2
3
Loop 2, Address M1 - M64
24
2
4
Loop 1, Address M65 - M128
25
2
5
Loop 2, Address M65 - M128
26
2
6
Loop 1, Address M129 - M159 &
Loop 2, Address M129 - M159
27
2
7
Loop 1, Address D1 - D64
28
2
8
Loop 2, Address D1 - D64
29
2
9
Loop 1, Address D65 - D128
30
3
0
Loop 2, Address D65 - D128
31
3
1
Loop 1, Address D129 - D159 &
Loop 2, Address D129 - D159