Alarm and trouble activation, Facp activations appendix b: ms-9200, Table 11 sw3 settings for alarm and trouble – Fire-Lite ACM-8RF Control Relay Module User Manual
Page 33

FACP Activations
Appendix B: MS-9200
ACM-8RF PN 50362:C 03/21/01
33
Alarm and Trouble Activation
Table 11 provides the switch settings for ACM-8RF DIP switch SW3 when
configuring the relays to trigger for MS-9200 alarm and trouble activation. A
maximum of 16 ACM-8RFs are required if relays are to be designated to trigger
on any FACP status change. If system status relays are not required, 14 ACM-
8RFs may be used to allow individual relay triggering for alarm and trouble
activation of FACP zones 1 through 56. When using 14 ACM-8RFs, be sure
to use the switch settings for the 3rd through the 16th ACM-8RF in Table 11.
When the MS-9200 is programmed for an annunciator without a UDACT-F,
the first 16 relays will be assigned to the status functions listed in the table
below.
If the MS-9200 is programmed for an annunciator and a UDACT-F, the first
16 relays will be assigned to the status functions listed in Table 12 on page 35.
MS-9200
Zone
ACM-8RF
Alarm
ACM-8RF
Trouble
Switch Settings
System Status
1=System Alarm
5=System Trouble
1st ACM-8RF
SW3-1 = ON;
SW3-5 = ON
All other SW3s = OFF
System Status
Relay 2 (not used)
6=Alarm Silence
System Status
Relay 3 (not used)
Relay 7 (not used)
System Status
Relay 4 (not used)
Relay 8 (not used)
System Status
Relay 1 (not used)
5= Supervisory
2nd ACM-8RF
SW3-2 = ON;
SW3-5 = ON
All other SW3s = OFF
System Status
Relay 2 (not used)
Relay 6 (not used)
System Status
Relay 3 (not used)
Relay 7 (not used)
System Status
Relay 4 (not used)
8= Panel Trouble
Z1
Relay 1
Relay 5
3rd ACM-8RF
SW3-3 = ON;
SW3-5 = ON
All other SW3s = OFF
Z2
Relay 2
Relay 6
Z3
Relay 3
Relay 7
Z4
Relay 4
Relay 8
Z5
Relay 1
Relay 5
4th ACM-8RF
SW3-4 = ON;
SW3-5 = ON
All other SW3s = OFF
Z6
Relay 2
Relay 6
Z7
Relay 3
Relay 7
Z8
Relay 4
Relay 8
Z9
Relay 1
Relay 5
5th ACM-8RF
SW3-1 = ON;
SW3-6 = ON
All other SW3s = OFF
Z10
Relay 2
Relay 6
Z11
Relay 3
Relay 7
Z12
Relay 4
Relay 8
Z13
Relay 1
Relay 5
6th ACM-8RF
SW3-2 = ON;
SW3-6 = ON
All other SW3s = OFF
Z14
Relay 2
Relay 6
Z15
Relay 3
Relay 7
Z16
Relay 4
Relay 8
Z17
Relay 1
Relay 5
7th ACM-8RF
SW3-3 = ON;
SW3-6 = ON
All other SW3s = OFF
Z18
Relay 2
Relay 6
Z19
Relay 3
Relay 7
Z20
Relay 4
Relay 8
Table 11 SW3 Settings for Alarm and Trouble