Facp activations, Alarm only activation, Table 10 sw3 settings for alarm only – Fire-Lite ACM-8RF Control Relay Module User Manual
Page 32

Appendix B: MS-9200
FACP Activations
32
ACM-8RF PN 50362:C 03/21/01
FACP Activations
DIP switch SW3 on the ACM-8RF Relay Control Module is used to determine
which FACP activations will trigger relays on the ACM-8RF. Use the following
tables to set SW3 switches. The Address Select Rotary Switches on all ACM-
8RFs must be set to address ‘01’ (SW1 = 0, SW2 = 1).
Two tables are provided, one table for alarm only operation (SW4-1 = ON) and
one table for alarm and trouble operation (SW4-1 = OFF).
Alarm Only Activation
Table 10 provides the switch settings for ACM-8RF DIP switch SW3 when
configuring the relays to trigger for MS-9200 alarm activation only. A
maximum of eight ACM-8RFs are required if one relay is to be designated to
trigger on any FACP zone alarm. If a general system alarm relay is not required,
seven ACM-8RFs may be used to allow individual relay triggering for alarm
activation of FACP zones 1 through 56. When using seven ACM-8RFs, be sure
to use the switch settings for the 2nd through the eighth ACM-8RF in Table 10.
Table 10 SW3 Settings for Alarm Only
MS-9200 Zone
ACM-8RF
Relay
ACM-8RF
SW3 Settings
MS-9200
Zone
ACM-8RF
Relay
SW3 Settings
System Alarm
Relay 1
1st ACM-8RF
SW3-1 = ON
SW3-5 = ON
All others =
OFF
Z25
Relay 1
5th ACM-8RF
SW3-1 = ON
SW3-6 = ON
All others =
OFF
Not Used
Relay 2
Z26
Relay 2
Not Used
Relay 3
Z27
Relay 3
Not Used
Relay 4
Z28
Relay 4
Not Used
Relay 5
Z29
Relay 5
Not Used
Relay 6
Z30
Relay 6
Not Used
Relay 7
Z31
Relay 7
Not Used
Relay 8
Z32
Relay 8
Z1
Relay 1
2nd ACM-8RF
SW3-2 = ON
SW3-5 = ON
All others =
OFF
Z33
Relay 1
6th ACM-8RF
SW3-2 = ON
SW3-6 = ON
All others =
OFF
Z2
Relay 2
Z34
Relay 2
Z3
Relay 3
Z35
Relay 3
Z4
Relay 4
Z36
Relay 4
Z5
Relay 5
Z37
Relay 5
Z6
Relay 6
Z38
Relay 6
Z7
Relay 7
Z39
Relay 7
Z8
Relay 8
Z40
Relay 8
Z9
Relay 1
3rd ACM-8RF
SW3-3 = ON
SW3-5 = ON
All others =
OFF
Z41
Relay 1
7th ACM-8RF
SW3-3 = ON
SW3-6 = ON
All others =
OFF
Z10
Relay 2
Z42
Relay 2
Z11
Relay 3
Z43
Relay 3
Z12
Relay 4
Z44
Relay 4
Z13
Relay 5
Z45
Relay 5
Z14
Relay 6
Z46
Relay 6
Z15
Relay 7
Z47
Relay 7
Z16
Relay 8
Z48
Relay 8
Z17
Relay 1
4th ACM-8RF
SW3-4 = ON
SW3-5 = ON
All others =
OFF
Z49
Relay 1
8th ACM-8RF
SW3-4 = ON
SW3-6 = ON
All others =
OFF
Z18
Relay 2
Z50
Relay 2
Z19
Relay 3
Z51
Relay 3
Z20
Relay 4
Z52
Relay 4
Z21
Relay 5
Z53
Relay 5
Z22
Relay 6
Z54
Relay 6
Z23
Relay 7
Z55
Relay 7
Z24
Relay 8
Z56
Relay 8