Fire-Lite ACM-8RF Control Relay Module User Manual
Page 29

Application Example #4
Appendix A: MS-5210UD
ACM-8RF PN 50362:C 03/21/01
29
Since each ACM-8RF module contains eight relays, two ACM-8RF modules
are required for 10 zones of Alarm Only Relays and three ACM-8RF modules
are required for 10 zones of Alarm and Trouble Relays (20 relays required).
Table 9 Settings for Zone Alarm and Trouble Activation with LED-10s
MS-5210UD
Zone
ACM-8RF
Alarm Relay
ACM-8RF
Trouble Relay
Switch Settings
Z1
Relay 1
1st ACM-8RF
SW1=0; SW2=3 (Address ‘03’)
SW3-2 = ON; SW3-5 = ON
All other SW3s = OFF
SW4-1=ON; SW4-2=ON
Z2
Relay 2
Z3
Relay 3
Z4
Relay 4
Z5
Relay 5
Z6
Relay 6
Z7
Relay 7
Z8
Relay 8
Z9
Relay 1
2nd ACM-8RF
SW1=0; SW2=3 (Address ‘03’)
SW3-3 = ON; SW3-5 = ON
All other SW3s = OFF
SW4-1=ON; SW4-2=OFF
Z10
Relay 2
n/a
Relay 3
n/a
Relay 4
n/a
Relay 5
n/a
Relay 6
n/a
Relay 7
n/a
Relay 8
Z1
Relay 1
Relay 5
3rd ACM-8RF
SW1=0; SW2=4 (Address ‘04’)
SW3-3 = ON; SW3-5 = ON
All other SW3s = OFF
SW4-1=OFF; SW4-2=ON
Z2
Relay 2
Relay 6
Z3
Relay 3
Relay 7
Z4
Relay 4
Relay 8
Z5
Relay 1
Relay 5
4th ACM-8RF
SW1=0; SW2=4 (Address ‘04’)
SW3-4 = ON; SW3-5 = ON
All other SW3s = OFF
SW4-1=OFF; SW4-2=ON
Z6
Relay 2
Relay 6
Z7
Relay 3
Relay 7
Z8
Relay 4
Relay 8
Z9
Relay 1
Relay 5
5th ACM-8RF
SW1=0; SW2=4 (Address ‘04’)
SW3-1 = ON; SW3-6 = ON
All other SW3s = OFF
SW4-1=OFF; SW4-2=OFF
Z10
Relay 2
Relay 6
n/a
Relay 3
Relay 7
n/a
Relay 4
Relay 8