Facp activations, Alarm only activation – Fire-Lite ACM-8RF Control Relay Module User Manual
Page 22

Appendix A: MS-5210UD
FACP Activations
22
ACM-8RF PN 50362:C 03/21/01
FACP Activations
DIP switch SW3 on the ACM-8RF Relay Control Module is used to determine
which FACP activations will trigger relays on the Relay Control Module.
When installed with an MS-5210UD Fire Alarm Control Panel, use the
following tables to set SW3 switches. Note that two tables are provided; one
table for alarm only operation (SW4-1 = ON) and one table for alarm and
trouble operation (SW4-1 = OFF).
Alarm Only Activation
Table 4 provides the switch settings for ACM-8RF DIP switch SW3 when
configuring the relays to trigger for alarm activation only. Note that a
maximum of three ACM-8RFs are required if one relay is to be designated to
trigger on any FACP alarm. If a general system alarm relay is not required, two
ACM-8RFs may be used to allow individual relay triggering for activation of
FACP zones 1 through 10. When using only two ACM-8RFs, be sure to use
the switch settings for the 2nd and 3rd ACM-8RF in Table 4. Refer to "Relay
Assignment DIP Switch - SW3" on page 15 for information on setting DIP
switch SW3.
Table 4 SW3 Settings for Alarm Only
MS-5210UD Zone
ACM-8RF Relay
SW3 Settings
System Alarm
Relay 1
1st ACM-8RF
SW3-1 = ON
SW3-5 = ON
All others = OFF
Not Used
Relay 2 (not used)
Not Used
Relay 3 (not used)
Not Used
Relay 4 (not used)
Not Used
Relay 5 (not used)
Not Used
Relay 6 (not used)
Not Used
Relay 7 (not used)
Not Used
Relay 8 (not used)
Z1
Relay 1
2nd ACM-8RF
SW3-2 = ON
SW3-5 = ON
All others = OFF
Z2
Relay 2
Z3
Relay 3
Z4
Relay 4
Z5
Relay 5
Z6
Relay 6
Z7
Relay 7
Z8
Relay 8
Z9
Relay 1
3rd ACM-8RF
SW3-3 = ON
SW3-5 = ON
All others = OFF
Z10
Relay 2
n/a
Relay 3 (not used)
n/a
Relay 4 (not used)
n/a
Relay 5 (not used)
n/a
Relay 6 (not used)
n/a
Relay 7 (not used)
n/a
Relay 8 (not used)