Edwards Signaling 877 User Manual

Description, Plc compatibility, Installation

background image

876 And 877 Grille Type Adaptahorn Installation
Sheet

Description

The 876 and 877 series are UL listed, FM approved, vibrating
horns in a NEMA Type 4X, 12, 12K rated enclosure. They are
low current, high decibel horns designed for heavy-duty use
either indoors or outdoors. The die-cast weatherproof box has
a durable, corrosion resistant, electrostatic heat flowed powder
epoxy gray finish. The horns are intended for general signaling
applications.

PLC Compatibility

The electrical input load requirements for PLC compatible
signaling devices are listed in Table 1. Signaling devices may
be directly connected to output cards that meet these load
requirements.

24V DC electromechanical horns such as the 877-G1 can
produce transient spikes and should only be used on PLC
output cards that have inherent transient spike suppression.
The Process Control Engineer should consult the PLC
manufacturer when connecting 24V DC electromechanical
devices to PLCs.

Installation

1. Using a 5/64" allen wrench (supplied), loosen both set

screws (located on either side of backbox) and remove
horn from backbox.

2. Fasten backbox to wall or partition as follows:

a. Remove the screw hole knockouts in the backbox.

b. Insert caplugs (supplied) in screw holes in backbox.

c.

Drive #8 wood screws (supplied) through caplugs into
mounting surface.

d. Secure conduit at entrance hole.

3. Ground the unit using the terminal screw in the box or by

other appropriate means.

4. Connect one wire to each terminal in backbox.

5. Orient the horn so that the "E" is at the top and plug horn

on backbox. Tighten set screws.

6. The volume is factory set at the maximum level. To

reduce volume level, turn set screw (located on grille front)
clockwise using a 1/16" allen wrench (supplied).

Table 1: PLC Compatibility

Catalog number

876-N5

877-G1

Operating voltage

120 VAC

24 VDC

Maximum off state
leakage current

25 mA

25 mA

Continuous on current

125 mA

160 mA

Surge (inrush/duration)

1.02 A/0.000026 ms 1.7 A/0.000042 ms

© 2011 UTC Fire & Security. All rights reserved.

1 / 2

P/N P-047550-1851 • REV 3.0 • ISS 28JUL11