Edwards Signaling B-8699 User Manual
Description, Electrical specifications, Installation
P-047550-1614 ISSUE 3 © 1998
Farmington, CT 203-699-3000 FAX. 860-677-7746
Installation Instructions for Catalog Series B-KM-8140 and B-8141
Explosion Proof Adaptabuzzers and B-8698 and B-8699 Weatherproof
Adaptabuzzers
Figure 1. Dimensions
DESCRIPTION
The Edwards Catalog Series B-KM-8140, B-8141, B-8699,
and B-8698 Adaptabuzzers are ideal for signaling use in areas
where extremely loud signals would be distracting. The B-
8698 and B-8699 and CS2690 Adaptabuzzers are gasket
sealed, weatherproof units. The B-8699 unit is UL Listed.
Coil Res.
Catalog Number
+
Volts
Amps
VA
(ohms)
B-KM-8140-E5*
12 AC 60 Hz
1.6
19.2
3.0
B-KM-8140-G5*
24 AC 60 Hz
1.1
26.4
5
B-KM-8140-N5*
120 AC 60 Hz
.2
24
146
B-KM-8140-R5*
240 AC 60 Hz
.1
24
740
B-8141-E1*
12 DC
1.6
19.2
3.0
B-8141-G1*
24 DC
.8
19.2
21.5
B-8141-P1*
125 DC
.2
25
110
B-8141-S1*
250 DC
.1
25
600
B-8699-E5*
12 AC 60 Hz
1.6
19.2
1.5
B-8699-G5*
24 AC 60 Hz
1.1
26.4
5
B-8699-N5*
120 AC 60 Hz
.2
24
146
B-8699-R5*
240 AC 60 Hz
.1
24
750
B-8698-E1
12 DC
1.5
18
4.8
B-8698-G1
24 DC
1
24
21.5
B-8698-P1
125 DC
.2
25
103.
B-8698-S1
250 DC
.1
25
600
CS2690
125 DC
.2
25
103
+
75 dB Min at 10 ft
* UL Listed
ELECTRICAL SPECIFICATIONS
The B-KM-8140 and B-8141 Adaptabuzzers are explosion proof
units and are listed for installation in the following hazardous
locations:
INSTALLATION
WARNING
To prevent electrical shock, ensure power is off before
starting installation.
1.
Mount the Adaptabuzzer assembly securely to a flat surface
in the desired location with (2) screws through the 3/8" (9.5
mm) diameter holes in the housing (Figure 1).
2.
Remove the unit's cover.
3.
Install conduit in 1/2" (12.7 mm) NPT tapped hole in side
of housing (3/4" (19 mm) NPT optional).
NOTE: Conduit runs must have a sealing fitting connected
within 18 inches of the enclosure.
4.
Using wire nuts, connect the ground wire to the green ground
wire attached to the Adatabuzzer housing; connect the
incoming power wires to the other two wire leads in
accordance with applicable local codes.
5.
Replace the unit's cover.
MAINTENANCE
WARNING
Ensure that all power is off before performing
maintenance.
1.
Inspect the unit at least once a year for damage or wear.
2.
Inspect all electrical and mechanical components for internal
corrosion or wire discoloration.
NOTE: When reassembling fixture, make certain that the
threads and taper joint between housing and brass
cover are clean.
Class
Zones
Divisions
Groups
I
1 and 2
C and D
I
1 and 2
IIA and IIB
II
1 and 2
E, F and G