4. Ground in accordance with national and local electrical
codes. A green ground screw is provided with both
the indoor and outdoor surface boxes.
5. Connect signaling circuit field wires to terminals on
horn assembly (Figures 2 and 3).
6. Mount the horn assembly on the mounting plate
(Figure 1).
a. The inside of the top of the grille has hinges that
pass through cutouts and engage with tabs on the
mounting plate. With the bottom of the grille
lifted out slightly, place the grille over the
mounting plate so that the hinges of the grille
are in the mounting cutouts.
b. Properly seat the grille by pressing the bottom in.
c. Fasten the bottom of the grille to the mounting
plate by installing the captive combination drive
screw.
7. Apply power and activate the horn/strobe unit to verify
that it is operating properly.
Maintenance
Maintenance
Maintenance
Maintenance
Maintenance
CAUTION
CAUTION
CAUTION
CAUTION
CAUTION
Should the unit fail to operate properly, do not attempt
repair. Contact the supplier for replacement.
Perform a visual inspection and an operational test twice
a year.
Table 2. Specifications
Operating Voltage
24V DC
Operating Current - Horn*
20 mA (low volume) @ 20 to 24V DC
40 mA (high volume) @ 20 to 24V DC
Sound Level Output at 10 ft. (3.05 m)
Anechoic Chamber
98 dBA peak (low volume)
102 dBA peak (high volume)
Operating Environment
Indoor
93% relative humidity @ 104F (40C); 32 to 120F
(0 to 49C) variable ambient temperature
Outdoor
98% relative humidity @ 104F (40C); -31 to 150F
(-35 to 66C) variable ambient temperature
*The operating voltage to the horn may be continuous or coded such as march time or a temporal pattern meeting
ISO8201 (ANSI S3.41) Audible Emergency Evacuation Signal.
Contacting Edwards:
Phone:
(203) 699-3000
E-Mail:
[email protected]
[email protected]
Website:
http://www.edwards-signals.com
Figure 2. Wiring Diagrams
Figure 3. Terminal Block
P/N 3100286 ISSUE 2
PAGE 2
4
HO
RN +
3
HO
RN -
2
NO
T
US
E
D
1
NO
T
US
E
D
REMOVE FOR
LOW OUTPUT
TEMPORAL TONE
FOR EMERGENCY
EVACUATION.
REMOVE FOR
CONT. TONE