Edwards Signaling 7008B-N5 User Manual
Warning
P-047550-1875 ISSUE 1 © 1999
CHESHIRE, CT 203-699-3300 FAX 860-677-7746
Installation Instructions for the
7008B-N5 Call for Assistance Package
Specifications
Horn/Strobe Voltage ................................................ 120V 60 Hz
Alarm Current .................................................................. 115 mA
Description
The 7008B-N5 120V AC Call for Assistance Package lets handi-
capped individuals alert the general area when they need emer-
gency assistance. The audible/visual-strobe device mounts out-
side and above the entrance of public rest room facilities. It sig-
nals an audible/visual alarm when the cord switch is pulled from
inside the facility. The kit contains a Pull Cord Switch (Cat. No.
6537) and an audible/visual signaling appliance (Cat. No. 7007B-
N5).
Installation
A qualified electrician familiar with National Electrical Code
and local code requirements must install this product. Failure to
follow the safety precautions in this instruction sheet could result
in product or property damage, severe personal injury or death.
WARNING
To reduce the risk of shock, do not connect AC power
until installation is complete.
WARNING
To reduce the risk of shock, do not remove lens or
tamper with unit when the circuit is energized.
Disconnect power and allow five (5) minutes for
stored energy to dissipate before starting work or
disassembly. High energy could be stored in the
strobe circuit once it is energized.
2.
Install Catalog No. 7007B-N5 horn/strobe (Figures 1 and 3).
1.
Install Cat. No. 6537 Pull Cord Switch (Figures 1 and 2).
a.
Install a single gang 2" x 4" (51 mm x 102 mm) electrical
box using suitable hardware.
b.
Extend the black and white wires using 18 AWG wire and
connectors (not supplied). Route the extended wires to
the horn/strobe and transformer (polarity is not important).
Ground in accordance with local codes and regulations.
c.
Mount the pull cord switch onto the electrical box using
two screws (supplied).
d.
If an additional Catalog No. 6537 pull cord switch is
required, install a single gang 2" x 4" (51 mm x 102 mm)
electrical box. Extend the black and white wires using
18 AWG wire and connectors (not supplied). Route the
extended wires to the previously installed pull cord switch
and connect the wire leads (Figure 1).
The 7007B-N5 horn/strobe can be mounted on any single
gang 2" x 4" (51 mm x 102 mm) electrical box, double gang
4" x 4" (102 mm x 102 mm) electrical box, or standard 4" x 4"
(102 mm x 102 mm) junction box with a plaster ring.
a.
Install an appropriate electrical box using suitable
hardware.
b.
Connect one wire from the 6537 pull cord to one of the
audible/visual signaling appliance wires (polarity is not
important).
c.
Extend the remaining audible/visual signaling appliance
wire to the 120V AC source.
d.
Mount the audible/visual signaling appliance onto the
electrical box using two screws (supplied).
4.
When all connections are completed, pull the cord switch and
verify operability of the audible/visual signaling appliance.
5.
Reset the unit using the switch on the cover of the Cat. No.
6537 Pull Cord (Figure 2).
Maintenance
Perform regularly scheduled testing at least twice a year or more
often as dictated by local authorities having jurisdiction.
The 7008B-N5 Call for Assistance Package is not serviceable or
repairable. Should it fail to operate properly, contact the supplier
for replacement.