Maintenance, Troubleshooting, Specifications – Edwards Signaling 51XBRF Series User Manual
Page 3: Regulatory information, Contact information

P/N 3101648 • REV 1.0 • ISS 03JAN12
3 / 4
Maintenance
WARNINGS
•
To prevent electrical shock, ensure that power is 
disconnected before installing the signal. 
•
To prevent leakage and potential electrical shock, use 
care when disassembling the signal to prevent tearing of 
the permanently affixed gaskets provided for 
weatherproofing. 
Horn replacement
Refer to Table 2 for the required horn. After disconnecting 
power, remove the old horn and attach the new one. Reattach 
the horn module wiring to the flasher module wiring. 
Cleaning
Caution:
To prevent damage to the lens, do not use abrasive
materials or cleaners.
The signal lens should be cleaned periodically to maintain 
optimum light visibility. It can be cleaned with a soft cloth or 
sponge using mild detergent. Dry the lens completely before 
replacing it. 
Table 2: Replacement parts
Catalog Number
51XBRF*120A
51XBRF*24D
Replacement horn
123A-N5
118-G1
Replacement lens
92-L*
92-L*
Solid state flasher module P-041917-0026
P-041917-0028
*Letter in this position designates lens and LED color = A = amber, B =
blue, W = white, G = green, R = red 
Troubleshooting
If the LED is flashing and the horn is not buzzing then the solid 
state flasher needs to be replaced. If after the replacement of 
solid state flasher the horn is still not buzzing, then the horn 
needs to be replaced. If the LED is not flashing and the horn is 
buzzing, then the LED circuit is damaged (the LED circuit is not 
offered as replacement part). 
Specifications
Catalog number
Electrical specs
Color
51XBRFA120A
120 VAC, 0.175 A
Amber
51XBRFB120A
120 VAC, 0.175 A
Blue
51XBRFG120A
120 VAC, 0.175 A
Green
51XBRFR120A
120 VAC, 0.175 A
Red
51XBRFW120A
120 VAC, 0.175 A
White
51XBRFA24D
24 VDC, 0.275 A
Amber
51XBRFB24D
24 VDC, 0.275 A
Blue
51XBRFG24D
24 VDC, 0.275 A
Green
51XBRFR24D
24 VDC, 0.275 A
Red
51XBRFW24D
24 VDC, 0.275 A
White
Regulatory information
 
Manufacturer 
Edwards, A Division of UTC Fire & Security 
Americas Corporation, Inc. 
8985 Town Center Parkway, Bradenton, FL 
34202, USA 
North American 
standards 
UL 1638
Contact information
For contact information see our Web site: 
www.edwardssignaling.com 