Edwards Signaling 200 Series Testing & Wiring User Manual
Series 200 safety switches, Testing & wiring instructions
S
AFE
T
Y
200 SERIES
42
1-800-336-4206
www.edwardssignalling.com
Testing
After mounting the switch and actuator, test the switch for proper
operation. Test with circuit disconnected from source and load. For
multiple switches in series, test one switch at a time with all other
guard doors closed. Then:
1. Hook the black and white leads of the switch to an Ohmmeter.
Move the gate or door open and closed several times slowly. At
all times the meter should read O.L. or “open.”
2. Hook the Ohmmeter to the black and red leads of the switch.
Move the door or gate open and closed. The meters should read
O.L. when the actuator is away and it should read less than 1
Ohm when the actuator is in range.
3. Hook the Ohmmeter to the white and red leads of the switch.
Move the door or gate open and closed. The meter should read
500-100 ohms when the actuator is away and it should read
O.L. when the actuator is in range.
Wiring
1. After the switch and actuator have been mounted and tested,
wire the FailSafe GuardSwitch
™
as shown in Figure 2.
2. For wiring 2 to 10 FailSafe GuardSwitches
™
in series, see Figure
3. (Do not exceed 10 switches in a series).
3. Failure to install in-line fuse voids warranty.
Troubleshooting
If the in-line fuse blows or the GuardSwitch
™
remains open:
1. Check the application for premature failure caused by
inrush-currents, tampering, excessive vibration and
misalignment.
2. Disconnect all three wires of GuardSwitch
™
and test according
to testing instructions, steps 1-3.
3. If the GuardSwitch
™
fails any of the three tests, it must be
replaced.
4. Replace the in-line fuse if blown.
Accessories
Part Number
Tamper proof screws & screwdriver
1953
#6 x 3/4"L Tampruf Roundhead Screw
1954
#8 x 1-1/2"L Tampruf Roundhead Screw
1955
Tampruf
®
Screwdriver
Wiring for two to ten FailSafe GuardSwitches
™
in series
Figure 3
Add a 1/2 amp fast-acting fuse in series to
protect the switch from premature failure caused
by inrush-currents, tampering, or excessive
vibration.
White
Black
Red
White
FailSafe
GuardSwitch
FailSafe
GuardSwitch
FailSafe
GuardSwitch
VAC/DC
Load
1/2A Fuse Required*
Black
Red
Red
Black
White
Wiring for one FailSafe GuardSwitch
™
Figure 2
Add a 1/2 amp fast-acting fuse
*
in series to
protect the switch from premature failure caused
by inrush-currents, tampering, or excessive
vibration.
*
Use fast-acting Littlefuse 216, fast-acting Microfuse or fast-acting
Pico II fuse up to 1/2 Amp.
Black
Red
1/2A Fuse Required*
FailSafe
GuardSwitch
Load
VAC/DC
White
Series 200 Safety Switches
Testing & Wiring Instructions
*
Use fast-acting Littlefuse 216, fast-acting Microfuse or fast-acting
Pico II fuse up to 1/2 Amp.
Accessories