Ordering/electrical specifications – Edwards Signaling 191 Series User Manual
Page 3

Ordering/Electrical Specifications
PART NUMBER
1
CONTACT
2
LOAD RATING
SWITCHING VOLTAGE
SWITCHING CURRENT
CONTACT
SENSE RANGE
3
BREAK RANGE
LEAD LENGTH
CONFIG.
AC/DC
MAXIMUM AC/DC
MAXIMUM AC/DC
RESISTENCE
NOMINAL
NOMINAL
NOMINAL
191-3Z-06K
N.C.
100VA/84W
4
3.0A
4
@34V
3.0 A
4
@28V
1.0 Ohms
0.5"(1.3cm)
1.8"(4.6cm)
6'(1.8m)
191-3Z-12K
N.C.
100VA/84W
4
3.0A
4
@34V
3.0A
4
@28V
1.0 Ohms
0.5"(1.3cm)
1.8"(4.6cm)
12'(3.6m)
191-4Z-06K
SPDT
100VA/84W
4
3.0A
4
@34V
3.0A
4
@28V
1.0 Ohms
0.5"(1.3cm)
1.8"(4.6cm)
6'(1.8m)
191-4Z-06K-D4
DPDT; 2SPDT
100VA/84W
4
3.0A
4
@34V
3.0A
4
@28V
1.0 Ohms
0.5"(1.3cm)
1.8"(4.6cm)
2@6'(1.8m)
191-4Z-12K
SPDT
100VA/84W
4
3.0A
4
@34V
3.0A
4
@28V
1.0 Ohms
0.5"(1.3cm)
1.8"(4.6cm)
12'(3.6m)
191-4Z-12K-D4
DPDT; 2 SPDT
100VA/84W
4
3.0A
4
@34V
3.0A
4
@28V
1.0 Ohms
0.5"(1.3cm)
1.8"(4.6cm)
2@12'(3.6m)
191-6Z-06(K)(A)
N.O.
25VA/25W
0.7A@35V
1.0 A@25V
0.2 Ohms
1.0"(2.5cm)
2.0"(5.1cm)
6'(1.8m)
191-6Z-12K
N.O.
25VA/25W
0.7A@35V
1.0A@25V
0.2 Ohms
1.0"(2.5cm)
2.0"(5.1cm)
12'(3.6m)
191-7Z-06K
N.O.
100VA/84W
4
3.0A
4
@34V
3.0A
4
@28V
1.0 Ohms
0.5"(1.3cm)
1.8"(4.6cm)
6'(1.8m)
191-7Z-06K-D3
DPST
6
N.O./N.C. 100VA/84W
4
3.0A
4
@34V
3.0A
4
@28V
1.0 Ohms
0.5"(1.3cm)
1.8"(4.6cm)
6'(1.8m)
191-7Z-12K
N.O.
100VA/84W
4
3.0A
4
@34V
3.0A
4
@28V
1.0 Ohms
0.5"(1.3cm)
1.8"(4.6cm)
12'(3.6m)
191-7Z-12K-D3
DPST N.O./N.C. 100VA/84W
4
3.0A
4
@34V
3.0A
4
@28V
1.0 Ohms
0.5"(1.3cm)
1.8"(4.6cm)
12'(3.6m)
191-8Z-06K
7
N.O./
150VA/NA
NA
1.25A@120V
5
NA
NA
1.0"(2.5cm)
2.1"(5.3cm)
6'(1.8m)
191-8Z-12K
7
N.O./
150VA/NA
NA
1.25A@120V
5
NA
NA
1.0"(2.5cm)
2.1"(5.3cm)
12'(3.6m)
191-17Z-06K
N.O.
100VA/100W
3.0A@34V
4
3.0A@34V
4
0.5 Ohms
0.5"(1.3cm)
1.8"(4.6cm)
6'(1.8m)
191-17Z-06K-D3
DPST N.O./N.C. 100VA/100W
3.0A
4
@34V
3.0A
4
@34V
0.5 Ohms
0.5"(1.3cm)
1.8"(4.6cm)
6'(1.8m)
191-17Z-12K
N.O.
100VA/100W
3.0A@34V
4
3.0A@34V
4
0.5 Ohms
0.5"(1.3cm)
1.8"(4.6cm)
12'(3.6m)
190-Z
Actuator Only
Included with all switches unless otherwise noted.
Warning— Each electrical rating is an individual maximum and cannot be exceeded!
1
The part number 193 is the same as 191 in all respects except the cable exits 191 left and 193 right.
2
Configuration with actuator away from the switch
3
Proximity of ferrous materials usually reduces sense range — typically by 50%. The shape and type
of material cause a wide diversity of effects.Testing is required to determine actual sense range
for specific applications.
4
Rated at 3.0A for 6,000 cycles only. Other ratings are at 100,000 cycles.
5
Can withstand inrush surge up to 4 amps. Voltage Drop 1.5V, minimum switch current 30mA.
6
DPST: 1 N.O., 1 N.C.
7
Maximum 10 switches in series.
triac
output
triac
output