beautypg.com

Edwards Signaling 156G User Manual

Edwards Signaling Safety

background image

CHESHIRE, CT 203-699-3000 FAX. 203-699-3075

Installation Instructions for the

Catalog Number 156 Monitor Bell

Figure 1.

INSTALLATION

CAUTION

Do not apply power to the bell until installation has

been completed.

1. If grounding is not required, remove the grounding strap

from the back of the bell as follows (See Figure 1):

a. Remove the #6-32 x 1/4" pan head screw securing the

ground strap.

b. Remove the adjacent terminal screw and remove the

grounding strap.

c. Replace the terminal screw removed in step 1b.

d. Replace the pan head screw removed in Step 1a with

(1) #6-32 x 3/8" nylon hex head screw (supplied).

2. For use in outdoor applications, install the weatherproof

gasket on the back of the bell.

3. Connect the bell to an appropriate AC or DC power source

using the terminal screws on the back of the bell.

4. Mount the bell to a flat surface using hardware appropriate

for the application.

5. Apply power and test the bell to ensure that it operates

properly.

MAINTENANCE

CAUTION

Always disconnect all power before servicing or

cleaning bell.

1. Examine the bell periodically for accumulation of dirt and

clean as necessary.

P-047550-1731 ISSUE 2

© 1996

US MODELS

Cat. No.*

Amps.

Volts

dB Rating

156G-3AM

.8A

6-8VDC 8-10VAC

72dBA

156G-3AX

.2A

12-18VDC

72dBA

156G-3E1

.3A

12VDC

72dBA

156G-3G1

.15A

24VDC

72dBA

156G-3G5

.3A

24VAC

72dBA

156G-3J1

.11A

32VDC

72dBA

156G-4AM

.8A

6-8VDC 8-10VAC

76dBA

156G-4E1

.3A

12VDC

76dBA

156G-4G1

.15A

24VDC

76dBA

156G-4G5

.3A

24VAC

76dBA

156G-6AM

.8A

6-8VDC 8-10VAC

80dBA

156G-6AW

.15A

20-24VDC

80dBA

156G-6E1

.3A

12VDC

80dBA

156G-6G1

.15A

24VDC

80dBA

156G-6G5

.3A

24VAC

80dBA

DESCRIPTION

The Edwards Catalog 156 Monitor Bells are insulated, grounded,

vibrating bells featuring a concealed plunger and a corrosion re-

sistant gray finish. The grounding strap may be removed if not

required. For outdoor applications the weatherproof gasket (pro-

vided) should be installed.

SPECIFICATIONS

CANADIAN MODELS

Cat. No.**

Amps.

Volts

dB Rating

156-AM

.8A

6-8VDC 8-10VAC

72dBA

156-G1

.15A

24VDC

72dBA

156-G5

.3A

24VAC

72dBA

* Bell gong size is denoted by suffix number. For example,

the156G-6G1 has a six inch gong.

** Canadian models provided with three inch gongs.