beautypg.com

Edwards Signaling 116EXST-EK User Manual

Page 4

background image

Table 1. 116 Series AdaptaBeacons

Catalog

Electrical

Conduit

Flash

Strobe Tube

Description

Number

Ratings

Size

Rate

Replacement

Housing Less

116EXST*-EK

12 - 48V DC

N/A

Approx.

92-ST

Mounting Module

1.2 - 0.38A

65 fpm

Ceiling/Wall

116EX-C

N/A

3/4" NPT

N/A

N/A

Mounting Module
Pendant

116EX-P

N/A

3/4" NPT

N/A

N/A

Mounting Module
Stanchion

116EX-S

N/A

1 1/4" NPT

N/A

N/A

Mounting Module

Wall Bracket

116EX-B

N/A

N/A

N/A

N/A

Mounting Elbow

*Letter in this position denotes color of the globe: A - amber, B - blue, C - clear, G - green, R - red or
M - magenta

P/N 3100757 ISSUE 1

Table 2. Ratings

Operating Temperature

Ambient

Supply Wire

Class I, Div. 2

Class I, Div. 1 & 2

Class II & III, Div. 1

Class II & III, Div. 2

Temp.

Temp. Marking

Groups A, B

Groups C, D

Groups E, F, G

Group G

40°C

75°C

T3 (200

°

C)

T6 (85

°

C)

T4A (120

°

C)

T4A (120

°

C)

55°C

90°C

T3 (200

°

C)

T6 (85

°

C)

T4 (135

°

C)

T4 (135

°

C)

65°C

105°C

T2D (215

°

C)

T6 (85

°

C)

T4 (135

°

C)

T4 (135

°

C)