Edwards Signaling 106DEX User Manual
Warning, Installation instructions for 106dex adaptabeacon
Operating Temperature Codes
Class II, Div. 2,
Groups F, G;
Class III, Div. 2
Class II, Div. 1,
Ambient Class I, Div. 1 & 2
Groups E, F, G;
Temp.
Groups C, D
Class III, Div. 1
40
°
C
85
°
C (T6)
120
°
C (T4A)
55
°
C
100
°
C (T5)
135
°
C (T4)
65
°
C
120
°
C (T4A)
135
°
C (T4)
P/N 3100098 ISSUE 2 © 2002
CHESHIRE, CT 203-699-3300 FAX 203-699-3365 (CUST. SERV.) 203-699-3078 (TECH. SERV.)
Installation Instructions for 106DEX AdaptaBeacon
®
Field Wiring Supervisable DC Rotating Lights for Use in
Hazardous Locations
Description
Description
Description
Description
Description
The 106DEX AdaptaBeacon 24-28V DC rotating signaling
appliances are heavy duty diode-polarized rotating lights
intended for use in general utility signaling (non-fire
alarm) applications requiring electrical supervision of sig-
naling circuit field wiring. The rotating assembly motor
driven at approximately 60 rpm. These devices are UL
and cUL listed for use in Class I, Division 1, Group C and D,
Class I, Division 2, Group C and D, Class II, Divisions 1 and
2, Group F and G, Class II, Division 1, Group E, and Class
III, Division 1 and 2 hazardous locations with Operating
Temperature Codes per the following chart.
Figure 1. Detail of Pendant Mounting
WARNING
To reduce the risk of ignition of hazardous atmo-
spheres and shock, do not apply power to the unit
until installation has been completed and unit is
tightly assembled and secured.
They are UL and cUL Listed as Type 3R, 4X, and Marine
enclosures.
Installation
Installation
Installation
Installation
Installation
WARNING
To reduce the risk of ignition of hazardous atmo-
spheres and shock, keep assembly tightly closed
when circuits are energized.
c. Bracket Mount Models (Figures 3 and 5):
Unscrew the globe assembly from the wall bracket.
Install the mounting bracket using appropriate
hardware (not supplied) for the mounting surface.
Pull the field wiring through the mounting
bracket. Proceed to step 2.
2. Extend the required power source wiring down
through the mounting hood. See Table 2 for required
supply wire temperature ratings.
3. Refer to Figure 5. Loosen the (2) screws holding the
circuit block in place. Rotate and remove the circuit
block.
4. Connect field earth ground wire to ground screw
(Figure 5) or earth ground via conduit system.
5. Wire in accordance with Figures 4 and 5. The positive
(+) terminal is gold colored and the negative (-)
terminal is silver colored.
6. Replace circuit block and tighten two screws to hold
in place.
7. Install the fixture on the mounting hood, bracket or
box as applicable.
8. Apply power to the unit and ensure proper function.
Install this unit in accordance with the applicable require-
ments in the latest edition of the National Electrical Code
and Canadian Electrical Code.
NOTE: This unit must be mounted with the globe
vertically facing up or down.
1. Mount using the following applicable method.
a. Pendant Mount Models (Figures 1 and 5):
Unscrew the globe assembly from the mounting
hood and set aside. Install explosion-proof hanger
box (not supplied). Secure 3/4" (19 mm) NPT
threaded conduit (not supplied) to the box. Install
the hood on the conduit. Proceed to step 2.
b. Ceiling Mount Models (Figures 2 and 5):
Unscrew the globe assembly from the ceiling
mount box. Mount the ceiling box using
appropriate hardware (not supplied) suitable for
the mounting surface. Proceed to step 2.
4.50"
(114.3mm)
13.15"
(334.01mm)
13.53"
(343.66mm)
7.80"
(198.12mm)