beautypg.com

Maintenance – Edwards Signaling Genesis Low Frequency 520 Hz Horn-Strobe User Manual

Page 2

background image

2 / 6

P/N 3102149-EN • REV 02 • ISS 25MAR14

To install the horn-strobe:

1. Remove the cover by using a screwdriver to depress and

slightly twist both tabs on top of the unit.

2. Set the horn signal, sound output level, and strobe signal

to the desired settings. See Figure 1.
To change the horn output level from high dB to low dB,

cut jumper JP3.
To change the horn signal from temporal to steady, cut

jumper JP2.
To change the strobe pattern from continuous to temporal

(private mode), cut jumper JP1.

3. Set the candela output.

Slide the candela switch to the desired candela output by

aligning it with the indicator notch below the switch. See

Figure 1.

4. Mount the horn-strobe as follows.

Note:

Route the signal circuit field wiring through the

cutout in the center of the horn-strobe.

Flush mount:

Mount the horn-strobe and flush mount

spacer onto a compatible electrical box (Figure 2), making

sure not to overtighten the mounting screws. See

“Specifications” for compatible electrical boxes.

Surface mount:

Mount the G4B or G4RB surface mount

box on the wall (Figure 3), and then secure the appliance

to the box using the fasteners provided with the box.

5. Connect the signal circuit field wiring to the horn-strobe

terminals (Figure 4). Observe polarity for the unit to

function properly.

6. Replace the cover by aligning it at the bottom, and then

snapping it in at the top.

7. Test the unit for proper operation.

Maintenance

Caution: To maintain the required agency listings, do not

change factory-applied finishes.

This unit is not serviceable or repairable. Should the unit fail to

operate, contact the supplier for a replacement.
Perform a visual inspection and an operational test twice a

year or as directed by the local authority having jurisdiction.

Figure 1: Horn-strobe settings

(1) Jumper JP3

(2) Jumper JP2

(3) Jumper JP1

(4) Candela switch indicator

notch

Figure 2: Flush mount

(1) Compatible electrical box

(2) Flush mount spacer

(3) Horn-strobe

(4) 8-32 x 1 in. screw, provided

(2X)

(5) Cover