Maintenance, Specifications – Edwards Signaling Genesis WG4 High-Candela Speaker-Strobe User Manual
Page 3
P/N 3101853 • REV 2.0 • ISS 21MAR11
3 / 4
Maintenance
This unit is not serviceable or repairable. Should the unit fail to
operate, contact the supplier for replacement.
Perform a visual inspection and an operational test twice a
year or as directed by the local authority having jurisdiction.
Caution:
Do not change the factory-applied finish.
Specifications
Operating voltage
Speaker
Default
Strobe
25 VRMS or 70 VRMS, switch selectable
70 VRMS
24 VDC, 24 VFWR nominal
Supervisory voltage
30 V max.
Sound level output
See Table 4
Speaker response
400 to 4,000 Hz
Strobe operating current See Table 8
Light output
Table 5, Table 6, and Figure 6
Wire size
12 to 18 AWG (0.75 to 2.50 mm²)
Compatible electrical
box
Wet
Dry
Model 449
4 in. square by 1-1/2 in. deep box
Operating environment
Temperature
Relative
humidity
Wet
−31 to 151°F (−35 to 66°C)
0 to 95% noncondensing
Table 3: Compatible synchronization sources models
Name Number
Auto-Sync Output
Module
SIGA-CC1S
GSA-MCC1S
GSA-CC1S
SIGA-CC2A
SIGA-MCC1S
SIGA-MCC2A
Genesis Signal
Master Remote
Mount
ADTG1M-RM
MG1M-RM
G1M-RM EG1M-RM
Table 4: Sound level output (dBA)
Wattage
Setting
25 V
70 V
2 W
T
90.0
89.7
1 W
X
87.1
86.9
1/2 W
Y
84.0
83.9
1/4 W
Z
80.8
80.8
dBA = Decibels, A-weighted.
UL 1480: Sound level output at 10 ft. (3.05 m) measured in a
reverberant room using 400 to 4,000 Hz band-limited pink noise.
Table 5: Indoor strobe output (cd)
Lens
Standard
D C B A
Clear UL
1971 102 123 147 161
Amber
UL
1638 84 101 125 130
Figure 5: Wiring, JP1, and switch locations
STROBE +
STROBE +
SPKR +
SPKR +
STROBE -
STROBE -
SPKR -
SPKR -
2
3
1
4
Detail A
5
1. Wire
slot.
2.
S1 wattage-setting switch (see Table 4).
3.
S2 candela-setting switch (see Table 5).
Note: Polarity shown in alarm condition
4.
JP1 strobe temporal mode selection jumper.
5.
S3 speaker voltage-setting switch. UP position is 70 V (default);
DOWN position is 25 V.