Wiring, Specifications, Regulatory information – Edwards Signaling E-IDC1B User Manual

Page 2: Contact information

background image

2 of 2

P/N 3101190 • REV 03 • ISS 25JAN13

Wiring

Wire in accordance with NFPA 72 and CAN/ULC-S524,
Standard for the Installation of Fire Alarm Systems and in
accordance with the local authorities having jurisdiction.

Be sure to observe the polarity of the wires as shown in
Figure 3.

All wiring is power-limited and supervised.

This module does not support two-wire smoke detectors.

Figure 3: Module wiring

47

EOL

k Ω

( )

0

1

2

3

4

5 6

12

11

10

9

8

7

0 9

1

2

3

4 5

6

7

8

3

2

4

1

1.

Refer to the control panel technical reference manual for wiring
specifications

2.

Wire nut or other listed splice connector or terminal block

3.

Style B (Class B)

4.

Typical NO initiating device

Specifications

Voltage

IDC maximum

Communication line

maximum


10 VDC at 350 µA
20.6 V peak-to-peak

Current

Standby
Activated


350 µA
500 µA

Ground fault impedance

10 kΩ

Initiating device circuit (IDC)

EOL resistor value
Circuit resistance
Circuit capacitance


47 kΩ, (P/N EOL-47)

50 Ω (25 Ω per wire), max.
0.1 µF, max.

Operating environment

Temperature
Relative humidity


32 to 120°F (0 to 49°C)
0 to 93%, noncondensing

Storage temperature range

–4 to 140°F (–20 to 60°C)

Regulatory information

Manufacturer

Edwards, A Division of UTC Fire & Security
Americas Corporation, Inc.
8985 Town Center Parkway, Bradenton, FL
34202, USA

Year of
manufacture

The first two digits of the product serial number
(located on the product identification label) are
the year of manufacture.

Environmental
class

UL: Indoor dry

North American
standards

UL 864; CAN/ULC-S526

Contact information

For contact information, see our Web site:
www.edwardssignaling.com.