P/N 3101180 • REV 02 • REB 28FEB13

Figure 3: Wiring detail for master to slave connection

(1) The maximum number of units that can be cascaded is 15.

(2) Switch SN1-1 through 6 and SN1-8 must be OFF for slave units.

(3) All power, supervisory and speaker connections remain

unchanged.

(4) Unsupervised wiring must be in the same cabinet, or in conduit

between cabinets that are in the same room and within a

maximum distance of 20 feet.

(5) A 14-pin ribbon cable (factory supplied) can be used in place of

hard-wired connections.

(6) J1 jumpers must be removed from slave units for pass-through

supervision.

Unsupervised and power-limited

TO ADDITIONAL

EXPANDER

UNITS (1)

TB1

TB3

MSG

GAIN

MIC

GAIN

FAULT (yellow)

NORMAL (green)

ALARM (red)

LED1

LED2

LED3

TB2

P2

S1

SN1

1 2 3

J2

70V 25V

+

+

+

+

1

2

3

4

5

6

7

8

1
2
3
4
5
6
7
8

1

2

3

4

5

6

7

8

9

10

11

FACP

EOLR

FACP

Polarity shown in alarm

NAC

A

B

J1

(5)

Supervised and power-limited

MASTER ANSX

A

B

TB1

TB3

MSG

GAIN

MIC

GAIN

FAULT (yellow)

NORMAL (green)

ALARM (red)

LED1

LED2

LED3

TB2

P2

S1

SN1 (2)

1 2 3

J2

J1

+

+

+

+

1

2

3

4

5

6

7

8

1
2
3
4
5
6
7
8

1

2

3

4

5

6

7

8

9

10

11

SLAVE ANSX

(6)

(3)

(4)