beautypg.com

Specifications – Edwards Signaling FSRZI-A-SA Remote Zone Indicators User Manual

Page 2

background image

2 / 2

P/N 3101032 • REV 02 • REB 25JAN13

Figure 1: Wiring diagram

1.

All wiring is supervised and power-limited.

[2] AUX power supplied by the control panel can’t exceed 0.5 A. If

more than 0.5 A is required, you must use a power-limited and
regulated 24 VDC auxiliary/booster power supply that is UL/ULC
Listed for fire protective signaling systems.

[3] If powered from an external supply, the supply must be installed

in the same room as the control panel and their 24 VDC
commons (−) wired together.

Figure 2: Installing the remote zone indicator in a single-gang
electrical box

Specifications


Voltage

18.8 to 27.3 Vdc

Current
Standby
Alarm


8 mA at 24 VDC
76 mA at 24 VDC

Circuit capacitance

0.03 µF, max.

Circuit resistance

13 ohms, max.

Ground fault impedance

0 ohms

Wire size

12 to 18 AWG (0.75 to 2.5 sq mm)

Compatible electrical box

ANSI/NEMA OS1-1996, 1- to 4-gang
electrical box

Operating environment
Temperature
Relative

humidity


32 to 120°F (0 to 49°C)
0 to 93% noncondensing

J5

J4
J3

J2

Regulated 24 VDC
from control panel or
external power supply
[2] [3]

From

control panel


C

C

To

next remote

module


C

C

Compatible 1-gang electrical box

FSRZI-A

or

FSRZI-SA

FSAT1