Edwards Signaling CTM City Tie Module User Manual

Page 2

background image

2 / 2

P/N 3101025 • REV 02 • REB 25JAN13

Figure 1: CTM installation wiring diagram

2

1

1

2

3

4

+

Active

Normal

Public fire alarm

reporting system

Local energy type

master box

+

+

+

EOLR [3]

Active

Normal

From dedicated notification
appliance circuit [4]

Compatible electrical box

CTM

Wall plate

Screws

14.5 Ω
trip coil

[1]

[2]

[1] Power-limited and supervised for opens, shorts, and ground faults

[2] Nonpower-limited and supervised for opens and ground faults

only. 26 Ω, max. 4.4 A, max.

[3] Use end-of-line resistor value required by the notification

appliance circuit

[4] NAC output signal must be compatible with the input rating of the

local energy type master box.